Parameter | OPC.GroupAddressType |
---|---|
Description | It defines the format that is used to map KNX group addresses to server item IDs. 2Level - uses the two-level KNX group address format 3Level - uses the three-level KNX group address format |
Scope | 2level, 3level |
Unit | None |
Default value | 3level |
The following examples represent the same KNX datapoint:
OPC.GroupAddressType: 2Level -> ITEM ID = "NETx\XIO\KNX\192.168.1.1\00/0513"
OPC.GroupAddressType: 3Level -> ITEM ID = "NETx\XIO\KNX\192.168.1.1\00/2/001"
Parameter | OPC.PrefixedItemID |
---|---|
Description | It defines whether the leading "0"-characters shall be added to server item IDs. ON - defines that leading "0"characters are added to the item IDs of KNX group addresses OFF - defines that the item IDs of KNX group addresses do not contain leading "0"-characters |
Scope | ON, OFF |
Unit | None |
Default value | ON |
The following examples represent the same KNX datapoint:
OPC.PrefixedItemID: ON -> ITEM ID = "NETx\XIO\KNX\192.168.1.1\00/2/001"
OPC.PrefixedItemID: OFF -> ITEM ID = "NETx\XIO\KNX\192.168.1.1\0/2/1"
Parameter | OPC.AsyncTimeout |
---|---|
Description | It defines the timeout value for asynchronous OPC queries. If no answer to an OPC query is received within this time interval, the quality of all queried datapoints will be set to UNCERTAIN. |
Scope | 1 - 60 |
Unit | seconds |
Default value | 5 |
Parameter | OPC.AsyncReadFromDevice |
---|---|
Description | It specifies whether the response data of the asynchronous OPC value read queries ("READ") shall be read from the server's data base, or whether it shall directly be retrieved from the field device. ON - the field devices are queried OFF - the values are read from the server's data base |
Scope | ON, OFF |
Unit | None |
Default value | OFF |
Parameter | OPC.AsyncRefreshFromDevice |
---|---|
Description | It specifies whether the response data of the asynchronous OPC value refresh queries ("REFRESH") shall be read from the server's data base, or whether it shall directly be retrieved from the field device. ON - the field devices are queried OFF - the values are read from the server's data base |
Scope | ON, OFF |
Unit | None |
Default value | OFF |
Parameter | OPC.ShowETSStructure |
---|---|
Description | It specifies whether to show an ETS like structure within the server item tree ON - shows the ETS like structure OFF - shows the NXA like structure |
Scope | ON, OFF |
Unit | None |
Default value | OFF |
Parameter | OPC.QualityForValueNotSet |
---|---|
Description | It specifies which OPC Quality value shall be used for item values that are not yet set. |
Scope | UNCERTAIN, BAD, NOT_CONNECTED |
Unit | None |
Default value | UNCERTAIN |
Parameter | OPC.Delimiter |
---|---|
Description | It specifies which delimiter shall be used for the item IDs within the server item tree. |
Scope | String (" not allowed) |
Unit | None |
Default value | \ |
!Attention: If the parameter is set on "ON", each OPC "WRITE" command will result in sending up telegrams to the field network. In the case of KNX, up to three KNX telegrams are sent.
Parameter | OPC.RefreshOnEqualValue |
---|---|
Description | It specifies whether OPC "OnDataChange" events are generated by incoming values from the field level even if the values are unchanged. ON - the "OnDataChange" of events will be generated OFF - the "OnDataChange" of events will be generated only with changes of value |
Scope | ON, OFF |
Unit | None |
Default value | ON |
Example:
If the server receives two KNX telegrams with same value and same address (IP + KNX group address) and the option "OPC.RefreshOnEqualValue" is set to "OFF", the OPC "OnDataChange" event is generated only for the first telegram, since the second telegram does not cause a change of value of the datapoint. If this option is set on "ON", then two OPC "OnDataChange" events are generated.
!Attention: Use the following option only with caution!
Parameter | OPC.AllValuesValid |
---|---|
Description | If set to "'ON"', server items always have the quality "'GOOD"', even if their quality is "'BAD"' or "'UNCERTAIN"'. This option can be used for limited OPC clients that are not aware of OPC qualities other than "'GOOD"'. |
Scope | ON, OFF |
Unit | None |
Default value | OFF |