Configuration
In addition to the common configuration options the following configuration options are available for each channel:
parameter | type | optional/mandatory | communication object | description | default |
---|---|---|---|---|---|
Fault General | ItemId | M | KNX Object #8, polled | True, if there is an error for at least 1 DALI device. | |
Fault DALI | ItemId | O | KNX Object #9 | True, if there is a general short cut on the DALI bus | |
Fault Lamps | ItemId | O | KNX Object #12 | True, if the amount of faulty devices with a lamps fault exceeds the configured threshold. | |
Fault Ballast | ItemId | O | KNX Object #14 | True, if the amount of faulty devices with a ballast fault exceeds the configured threshold. | |
Fault Converter | ItemId | O | KNX Object #16 | True, if the amount of faulty emergency lights with a converter fault exceeds the configured threshold. | |
Error Status Lamp/Ballast | ItemId | M | KNX Object #20 | ||
EmergencyTestTimeout | int | O | Specifies how long the driver will wait between sending two emergency start requests. | 10 s |
Since the communication objects #12, #14 and #16 are only getting true when a configured threshold is exceeded, it is of utmost importance to configure them correctly. In general, it is recommended to use a threshold of 1 in order to see all lamp faults.
Since these gateways do not have a global KNX communication object for starting an emergency test and for getting the result (they have a separate object for each device), the ItemIDs has to be configured for each emergency lighting separately. This is done in the 944735036.