Configuration

In addition to the common configuration options the following configuration options are available for each channel:

parametertypeoptional/mandatoryPolleddescriptiondefault
Fault GeneralItemIdMyesTrue, if there is an error for at least 1 DALI device.
Fault DALI ItemIdOnoTrue, if there is a general short cut on the DALI bus
Fault LampsItemIdOnoTrue, if the amount of faulty devices with a lamps fault exceeds the configured threshold.
Fault BallastItemIdOnoTrue, if the amount of faulty devices with a ballast fault exceeds the configured threshold.
Fault ConverterItemIdOyesTrue, if the amount of faulty emergency lights with a converter fault exceeds the configured threshold.
Error Status Lamp/BallastItemIdMno

Emergency Test IntervalintO
Specifies how long the driver will wait between sending two emergency start requests.10 s


ManufacturerTypeEmergencyFault GeneralFault DALI Fault LampsFault BallastFault ConverterError Status Lamp/BallastEmergency StartEmergency Result
Ipas


DaliControl e64 (plugin version)yes#8#9#12#14#16#20#176, offset: 11#177, offset: 11
DaliControl e64yes#13#14#17#19#21#29#490, offset: 13#491, offset: 13
DaliControl gc16no#10#11#14#16NA#20NANA
DaliControl gc16-2no#12, #652#13, #653#16, #656#18, #658NA#22, #662NANA
Merten

DALI gateway REG-K/1/16(64)/64/IP1 (plugin version)yes#8#9#12#14#16#20#176, offset: 11#177, offset: 11
DALI-Gateway Basic REG-K/1/16/64no#10#11#14#16NA#20NANA
DALI Gateway Basic REG-K/2/16/64no#12, #652#13, #653#16, #656#18, #658NA#22, #662NANA
Schneider

DALI gateway REG-K/1/16(64)/64/IP1 (plugin version)yes#8#9#12#14#16#20#176, offset: 11#177, offset: 11
DALI-Gateway Basic REG-K/1/16/64no#10#11#14#16NA#20NANA
DALI Gateway Basic REG-K/2/16/64no#12, #652#13, #653#16, #656#18, #658NA#22, #662NANA
MDTDali Control IP 64 (plugin version)yes#8#9#12#14#16#20#176, offset: 11#177, offset: 11
Dali Control IP 64yes#13#14#17#19#21#29#490, offset: 13#491, offset: 13
Dali Control 32no#12, #652#13, #653#16, #656#18, #658NA#22, #662NANA
Dali Control 16no#10#11#14#16NA#20NANA
B.E.G.DALI/KNX Gateway IP-Nyes#8#9#12#14#16#20#176, offset: 11#177, offset: 11


 Since the communication objects #12, #14 and #16 are only getting true when a configured threshold is exceeded, it is of utmost importance to configure them correctly. In general, it is recommended to use a threshold of 1 in order to see all lamp faults.


Since these gateways do not have a global KNX communication object for starting an emergency test and for getting the result (they have a separate object for each device), the ItemIDs has to be configured for each emergency lighting separately. This is done in the 944735036.

Functional description

These KNX/DALI gateway types provide 1 DALI channel with up to 64 DALI devices. In addition to normal DALI testing, they support emergency lighting and extended tests for emergency lighting too.

For all these gateway types, the following Server Items are available:

item namedescription
KNX IP ConnectionThis Item reflects the KNXnet/IP tunneling connection to KNXnet/IP router or interface which is used to communicate with the KNX/DALI gateway.
FaultTrue, if there is either a DALI, lamp, or ballast fault.
Fault DALITrue, if there is a general short cut on the DALI bus.
Fault DevicesTrue, if there is a lamp or ballast fault for at least 1 DALI device.
Fault Lamp

True, if the amount of lamp faults exceeds the configured threshold. If exceeded, LaMPS is starting to test all configured devices in order to see which device(s) have a fault. 

Fault BallastTrue, if the amount of ballast faults exceeds the configured threshold. If exceeded, LaMPS is starting to test all configured devices in order to see which device(s) have a fault. 
Fault ConverterTrue, if there is a converter fault of one or more DALI devices.  

Since these gateways also support emergency lighting, it has to be distinguished between a normal DALI test and an emergency DALI test.

Unable to render {include} The included page could not be found.

For emergency DALI testing, the following Server Items are available under the sub tree "Emergency":

item namedescription
Start Function TestUsed to trigger a function test for all emergency DALI lights.
Start Duration TestUsed to trigger a duration test for all emergency DALI lights.
Start Battery TestUsed to trigger a battery test for all emergency DALI lights.
Stop TestUsed to stop a running test.
Emergency Light Test RunningTrue, when an emergency DALI test is currently running.


Please keep in mind that these items will only appear when emergency testing is available for the gateway. For these KNX/DALI gateways at least one DALI device must support emergency lighting tests. This means that there must be a "Emergency Mapping Definition" for at least one DALI device. Note that emergency testing is only available for self contained battery lamps.

For each configured DALI device, a sub tree with the name "Device<number>" is shown within the Server Item Tree. Each device has at least the following Server Items:

item namedescription
NameHuman-readable name of the DALI device. The default name is "Device<number>". This name can be changed within the Device Name Mapping Definitions. 
FaultTrue, if either a lamp or a device fault occurred.
Fault LampTrue, if there is a lamp fault.
Fault BallastTrue, if there is a device fault.
Test succeededTrue, if a response is received during the test.

If a device is also an emergency light (i.e. it has a valid emergency mapping definition), the following items are available in the sub tree "Emergency":

item namedescription
Test RunningTrue, when an emergency DALI test is currently running.
Start Function TestUsed to trigger a function test for this device.
Start Duration TestUsed to trigger a duration test for this device.
Start Battery TestUsed to trigger a battery test for this device.
Stop TestUsed to stop a running test.
Last test was

Shows the type of the last test. 

value

description

0"No Test"
1"Function Test"
2"Partial duration test"
3"Duration test"
4"Battery test"
255"Test not supported"
Last test faultedTrue, if there was no test result response. This may be the case when the DALI does not support emergency tests.
Converter defectTrue, if the converter is defect.
Fault batteryTrue, if there is a battery fault.
Battery defectTrue, if the battery is defect.
Fault emergency lightTrue, if there is an emergency light failure.
Max time function test exceededTrue, if the maximum time for the function test exceeded.
Max time duration test exceededTrue, if the maximum time for the duration test exceeded.
Function test failedTrue, if the function test failed.
Duration test failedTrue, if the duration test failed.
Test resultTest result: The raw data as received from the gateway. Time results have to be multiplied by 2 minutes; Battery charge status is from 0 to 255 and has to be converted to percentage.

Unable to render {include} The included page could not be found.