Name | Description | Scope | Unit | Default | Notes |
---|---|---|---|---|---|
SYS.SendVirtualTelegrams | Enables or disables the sending of telegrams for KNX main group addresses above 15. | ON, OFF | None | OFF | |
SYS.MaxSizeOfTelegramLogFile | Specifies the maximum size of the telegram log file. If size is exceeded, new records overwrite oldest records. | 1 - 1000 | MB | 10 | |
SYS.SpinTelegramFile | If enabled a new telegram log file is created every day. | ON, OFF | None | ON | |
SYS.EnableDeviceManager | Enables the physical KNX device management. ON - the physical device management is enabled OFF - the physical device management is disabled | ON, OFF | None | ON | |
SYS.OPCInterfaceEnabled | Enables the OPC Server. | ON, OFF | None | ON | |
SYS.GenerateRandomValues | If the server is running in simulation mode and this parameter is set to "ON", the server generates random values for all server items. ON - the server generates random values if the server is running OFF - The server does not generate random values | ON, OFF | None | ON | |
SYS.EnableOperationTime | The server will calculate the operation time in seconds of KNX datapoints that are of type EIS1. ON - the operation time calculation is enabled OFF - the operation time calculation is disabled | ON, OFF | None | OFF | |
SYS.CodePage | Defines the code page that is used within the NETx BMS Core Server. Value of 0 indicates to use the Windows system code page. | 1 - 65535 | None | 0 | Modifying this value is not recommended. From version 4.2.1020 on this parameter is therefore hidden. |
SYS.LoggingLevel | System logging level for providing additional output to server logs | -65535 - 65535 | None | 0 | |
SYS.GeoLatitude | Specifies the geographic latitude in degrees (+ is used for north, - for south) | 0 - 360 | degrees | 0 | |
SYS.GeoLongitude | Specifies the geographic longitude in degrees (+ is used for east, - for west) | 0 - 360 | degrees | 0 | |
SYS.GeoElevation | Specifies the geographic elevation in meters. | 0 - 10000 | m | 0 | |
SYS.OPCBridgeStartDelay | Delay (in seconds) for connecting to the configured OPC DA server for clustering | 0 - 600 | seconds | 10 | Available since R2 Build 2010 |
! Following SYSTEM parameters are available only for compatibility reasons and may be removed in future versions. | |||||
SYS.GatewayConnectionTimeout | Specifies the timeout value for availability check of the connected KNXnet/IP routers. | 10 - 10000 | ms | 500 | |
SYS.GatewayConnectionTimeoutAttemptCount | Specifies the number of call attempts for the availability check of the connection of the connected KNXnet/IP routers in the case of an interruption. | 1 - 10 | None | 3 | |
SYS.SpinLogFile | ON - the system log file switches to a new file every day. OFF - the system log file remains in the same file as long as the server is running. | ON, OFF | None | OFF |
Article applies to the following products:
- NETx BMS Platform