NameDescriptionScopeUnitDefaultNotes
SYS.SendVirtualTelegramsEnables or disables the sending of telegrams for KNX main group addresses above 15.ON, OFFNoneOFF
SYS.MaxSizeOfTelegramLogFile

Specifies the maximum size of the telegram log file. If size is exceeded, new records overwrite oldest records.

1 - 1000MB10
SYS.SpinTelegramFileIf enabled a new telegram log file is created every day.ON, OFFNoneON
SYS.EnableDeviceManager

Enables the physical KNX device management. ON - the physical device management is enabled OFF - the physical device management is disabled

ON, OFFNoneON
SYS.OPCInterfaceEnabledEnables the OPC Server.ON, OFFNoneON
SYS.GenerateRandomValuesIf the server is running in simulation mode and this parameter is set to "ON", the server generates random values for all server items. ON - the server generates random values if the server is running OFF - The server does not generate random valuesON, OFFNoneON
SYS.EnableOperationTimeThe server will calculate the operation time in seconds of KNX datapoints that are of type EIS1. ON - the operation time calculation is enabled OFF - the operation time calculation is disabledON, OFFNoneOFF
SYS.CodePageDefines the code page that is used within the NETx BMS Core Server. Value of 0 indicates to use the Windows system code page.1 - 65535None0Modifying this value is not recommended. From version 4.2.1020 on this parameter is therefore hidden.
SYS.LoggingLevelSystem logging level for providing additional output to server logs-65535 - 65535None0
SYS.GeoLatitudeSpecifies the geographic latitude in degrees (+ is used for north, - for south)0 - 360degrees0
SYS.GeoLongitudeSpecifies the geographic longitude in degrees (+ is used for east, - for west)0 - 360degrees0
SYS.GeoElevationSpecifies the geographic elevation in meters.0 - 10000m0
SYS.OPCBridgeStartDelayDelay (in seconds) for connecting to the configured OPC DA server for clustering0 - 600seconds10Available since R2 Build 2010
SYS.PersistentValueTransactionIntervalTransaction interval for persistent values0 - 60seconds1Available since R2 Build 2060
! Following SYSTEM parameters are available only for compatibility reasons and may be removed in future versions.
SYS.GatewayConnectionTimeoutSpecifies the timeout value for availability check of the connected KNXnet/IP routers.10 - 10000ms500
SYS.GatewayConnectionTimeoutAttemptCountSpecifies the number of call attempts for the availability check of the connection of the connected KNXnet/IP routers in the case of an interruption.1 - 10None3
SYS.SpinLogFileON - the system log file switches to a new file every day. OFF - the system log file remains in the same file as long as the server is running.ON, OFFNoneOFF