Configuration

In addition to the common configuration options the following configuration options are available for each channel:

parametertypeoptional/mandatorycommunication objectdescriptiondefault
Fault GeneralItemIdMKNX Object #8, polledTrue, if there is an error for at least 1 DALI device.
Fault DALI ItemIdOKNX Object #9True, if there is a general short cut on the DALI bus
Fault LampsItemIdOKNX Object #12True, if the amount of faulty devices with a lamps fault exceeds the configured threshold.
Fault BallastItemIdOKNX Object #14True, if the amount of faulty devices with a ballast fault exceeds the configured threshold.
Fault ConverterItemIdOKNX Object #16True, if the amount of faulty emergency lights with a converter fault exceeds the configured threshold.
Error Status Lamp/BallastItemIdMKNX Object #20

EmergencyTestTimeoutintO
Specifies how long the driver will wait between sending two emergency start requests.10 s


 Since the communication objects #12, #14 and #16 are only getting true when a configured threshold is exceeded, it is of utmost importance to configure them correctly. In general, it is recommended to use a threshold of 1 in order to see all lamp faults.


Since these gateways do not have a global KNX communication object for starting an emergency test and for getting the result (they have a separate object for each device), the ItemIDs has to be configured for each emergency lighting separately. This is done in the 944735036.

Functional description