EAE DA 110

Configuration

In addition to the common configuration options the following configuration options are available for each channel:

parametertypeoptional/mandatorycommunication objectdescriptiondefault
Fault LampItemIdMKNX Object #14, polledTrue, if there is a lamp error for at least 1 DALI device.
Fault BallastItemIdMKNX Object #15, polledTrue, if there is a ballast error for at least 1 DALI device.
Fault ConverterItemIdOKNX Object #16, polledTrue, if there is a converter error for at least 1 DALI device.
Fault Gateway SupplyItemIdOKNX Object #12True, if there is a general DALI error.
Fault Mains ConnectedItemIdOKNX Object #13True, if there is a mains connected supply error.
Device StatusItemIdMKNX Object #7Used to trigger a normal DALI request and to get the test result.
Emergency Test StartItemIdOKNX Object #2Used to trigger an emergency DALI test.
Emergency Test IntervalintO
Specifies how long the driver will wait between sending two emergency start requests.10 s

Functional description

refer to EAE DA 100