The order of bits, bytes, words as well as endianess are not specified by the Modbus standard. These configurations have to be made according to the modbus device specifications.
If the word order is wrong the typically floating-point values such as temperature readings are reveiced but the values make no sense.
In that case, go to BMS Core Studio / Modbus / Device definitions and change the setting for Wordswap for the respective device, save the table and restart the BMS Server.