DALI gateway server items for emergency lighting

For emergency DALI testing, the following Server Items are available under the Emergency branch:

item name

description

Start Function Test

Used to trigger a function test for all emergency DALI lights.

Start Partial Duration Test

Used to trigger a partial duration test for all emergency DALI lights.

Start Duration Test

Used to trigger a duration test for all emergency DALI lights.

Start Battery Test

Used to trigger a battery test for all emergency DALI lights.

Stop Test

Used to stop a running test.

Test Running

True, if an emergency DALI test is currently running.

Fault

True, if an emergency test of at least 1 DALI light failed.

Last test faulted

True, if "Last test faulted" of at least 1 DALI light is currently true.

Converter defect

True, if "Converter defect" of at least 1 DALI light is currently true.

Battery fault or defect

True, if "Battery fault or defect" of at least 1 DALI light is currently true.

Fault emergency light

True, if "Fault emergency light" of at least 1 DALI light is currently true.