Configuration
In addition to the common configuration options the following configuration options are available for each channel:
parameter | type | optional/mandatory | communication object | description | default |
---|---|---|---|---|---|
Fault General | ItemId | M | KNX Object #1524, polled | True, if there is an error for at least 1 DALI device. | |
Fault Short Circuit | ItemId | O | KNX Object #1527 | True, if there is a general short cut on the DALI bus. | |
Fault Power Failure | ItemId | O | KNX Object #1525 | True, if there is a power failure on the DALI bus. | |
Emergency Mode Active | ItemId | O | KNX Object #1541 | True, if DALI devices are in emergency mode. | |
Emergency Lighting Failure | ItemId | O | KNX Object #1542 | True, if there is an error for at least 1 emergency DALI device. This config element is optional. If it is not used, emergency lighting test features are not available. | |
Error per DALI Device | ItemId | M | KNX Object #1544 | KNX feedback object for DALI device errors. | |
EmergencyTestTimeout | int | O | Specifies how long the driver will wait between sending two emergency start requests. | 10 s |
The objects Fault General (#1524) and Emergency Lighting Failure (#1542) can be configured as passive or active feedback objects. If at least one of them is set as passive, "Poll Device" should be set to true.
The objects Fault General (#1524) and Error per DALI Device (#1544) needs to be linked to a group address. Otherwise the dali gateway will be seen as "not used" and therefore be ignored for the export.
Since these gateways do not have a global KNX communication object for starting an emergency test and for getting the result (they have a separate object for each device), the ItemIDs has to be configured for each emergency lighting separately. This is done in the 944735036.