Configuration

In addition to the common configuration options the following configuration options are available for each channel:

parametertypeoptional/mandatorycommunication objectdescriptiondefault
Fault GeneralItemIdMKNX Object #1524, polledTrue, if there is an error for at least 1 DALI device.
Fault Short CircuitItemIdOKNX Object #1527True, if there is a general short cut on the DALI bus.
Fault Power FailureItemIdOKNX Object #1525True, if there is a power failure on the DALI bus.
Emergency Mode ActiveItemIdOKNX Object #1541True, if DALI devices are in emergency mode.
Emergency Lighting FailureItemIdOKNX Object #1542True, if there is an error for at least 1 emergency DALI device. This config element is optional. If it is not used, emergency lighting test features are not available.
Error per DALI DeviceItemIdMKNX Object #1544KNX feedback object for DALI device errors.
EmergencyTestTimeoutintO
Specifies how long the driver will wait between sending two emergency start requests.10 s

The objects Fault General (#1524) and Emergency Lighting Failure (#1542) can be configured as passive or active feedback objects. If at least one of them is set as passive, "Poll Device" should be set to true.

The objects Fault General (#1524) and Error per DALI Device (#1544) needs to be linked to a group address. Otherwise the dali gateway will be seen as "not used" and therefore be ignored for the export.

Since these gateways do not have a global KNX communication object for starting an emergency test and for getting the result (they have a separate object for each device), the ItemIDs has to be configured for each emergency lighting separately. This is done in the 944735036.