To make the configuration of BACnet devices and their objects more easier, a tool called BACnet Explorer is provided. Starting with BMS Platform and MP Server version R2 Build 2068, this tool can be used to discover BACnet devices and their objects online or BACnet EDE files can be imported.

...

Start the Core Server and open an Item Tree. All BACnet devices and objects are found under the branch NETx\XIO\BACnet. Each device has one entry within the Item Tree. Below this entry a GATEWAY item shows the connection state of the BACnet device. In addition, all selected objects are listed. As defined by the BACnet standard some BACnet objects are read-only (e.g Binary Input, Analog Input, ...) and some are also writable (e.g. Binary Output, Analog Output, ...). Input objects have only one item which shows the current Present Value of the BACnet object. Output objects have in addition for each used BACnet priority one Write Item to send a write command with the given priority and one Reset Item to reset the given priority. The NETx BMS Server supports multiple priorities at the same time. The following figure shows an example.

...

Info

BACnet PIC statement

The BACnet Protocol Implementation Conformance statement (BACnet PIC statement) is a standardized document that describes all BACnet services and BACnet object types supported by a certain BACnet product. This document is used to prove that a BACnet client is able to communicate with a BACnet device and that all required functions have been implemented. The BACnet PIC of the NETx BMS Core Server can be found at our web site.