Within this configuration, all Fidelio settings are specified. Each parameter is identified with a name. The name is case-insensitive (i.e. capitalization is not considered). The scope indicates the allowed values of the parameter. The default value specifies the values that is used when no value is set by the user.
The parameters which can be defined in this file are divided into the following two groups:

  • FIDELIO
  • SYS

FIDELIO-Parameters

 

Parameter

FIDELIO.IPAddress

Description

This defines
ParameterDescriptionScopeUnit

Default value

IPAddressSpecifies the IP address of the
FIDELIO or OPERA Unit
Fidelio/Opera server.

Scope

###.###.###.

IP addressNone

Default value

None

Parameter

FIDELIO.
Port

Description

This defines
Specifies the TCP port number of the
FIDELIO or OPERA
Fidelio/Opera server.
Scope
### (
1-65535
)

Unit

None

Default value

5018

Parameter

FIDELIO.Logging

Description

This enables the logging of the data telegrams from the FIDELIO or OPERA server.

Scope

ON/OFF

Unit

None

Default value

ON

Parameter

FIDELIO.LRC

Description

This turns on or off LRC for the data telegrams.

Scope

ON/OFF

Unit

None

Default value

OFF

Parameter

FIDELIO.UpdateOnReconnect

Description

If set data from FIDELIO or OPERA server are called to update the information inside the NETx BMS Core Server when the connection to the FIDELIO or OPERA server is reestablished.

Scope

ON/OFF

Unit

None

Default value

OFF
None5003
LRCTurns LRC for data telegrams on or off.ON/OFFNoneOFF
LoggingEnables logging of data telegrams to and from the Fidelio/Opera server.ON/OFFNoneOFF
UpdateOnReconnectIf set, when the connection to the Fidelio/Opera server is (re-)established data from Fidelio/Opera server are queried to update the information in the NETx BMS Core Server.ON/OFFNone

ON

UseControlByteEnables the acknowledged transmission of data telegrams.ON/OFFNoneOFF
UseGCEnables or disables the use of "Guest Change (GC)" records.ON/OFFNone

ON

UseLinkCheckIf enabled, the BMS server sends an "LS" record for keep alive checking in a cyclic interval. The interval can be defined by FIDELIO.AliveInterval.ON/OFFNoneOFF
UseLALinkCheckUse "LA" keep alive checking;T;If enabled, the BMS server sends an "LA" record for keep alive checking in a cyclic interval. The interval can be defined by FIDELIO.AliveInterval.ON/OFFNone

ON

AliveIntervalDefines the interval in seconds for keep alive checking.1 - 65535seconds300
CommandTimeoutDefines command timeout in seconds used for start up and acknowledged transmission.1 - 65535seconds3
MessagesEnabledIf enabled, messages to and from Fidelio/Opera can be sent or received.ON/OFFNone

ON

RoomStatusEnabledIf enabled, it is request to use RE (room equipment) records.ON/OFFNone

ON

UsedGIRecordsDefines which optional fields shall be sent by Fidelio/Opera within GI records. Use <NONE> if no additional optional fields shall be sent.stringNoneGAGDGFGLGNGTGVNPSFDATI
UsedGCRecordsDefines which optional fields shall be sent by Fidelio/Opera within GC records. Use <NONE> if no additional optional fields shall be sent.stringNoneROGAGDGFGLGNGTGVNPDATI
UsedGORecordsDefines which optional fields shall be sent by Fidelio/Opera within GO records. Use <NONE> if no additional optional fields shall be sent.stringNoneSFDATI
UsedRERecordsDefines which optional fields shall be sent by Fidelio/Opera within RE records. Use <NONE> if no additional optional fields shall be sent.stringNoneG#CSDNRSCTVMPPML


 

SYSTEM-Parameters

Parameter

SYS.RefreshInterval

Description

This defines
DescriptionScopeUnit

Default value

RefreshInterval

Defines the time between

one call

two calls for data

and the next one

to the

FIDELIO or OPERA

Fidelio/Opera server.

Scope

Unit

numeric

###

seconds
Default value
20