Fidelio Driver Configuration
Fidelio Driver Configuration
Within this configuration file, general settings for the Fidelio/Opera interface are configured.
File location
<WorkspaceDirectory>\ConfigFiles\nxapiFidelio.cfg
Parameter | Description | Scope | Unit | Default value |
---|---|---|---|---|
FIDELIO.IPAddress | Specifies the IP address of the Fidelio/Opera server. | IP address | None | None |
FIDELIO.Port | Specifies the TCP port number of the Fidelio/Opera server. | 1-65535 | None | 5003 |
FIDELIO.LRC | Turns LRC for data telegrams on or off. | ON/OFF | None | OFF |
SYS.RefreshInterval | Defines the time between two calls for data to the Fidelio/Opera server. | numeric | seconds | 20 |
FIDELIO.Logging | Enables logging of data telegrams to and from the Fidelio/Opera server. | ON/OFF | None | OFF |
FIDELIO.UpdateOnReconnect | If set, when the connection to the Fidelio/Opera server is (re-)established data from Fidelio/Opera server are queried to update the information in the NETx BMS Core Server. | ON/OFF | None | ON |
FIDELIO.UseControlByte | Enables the acknowledged transmission of data telegrams. | ON/OFF | None | OFF |
FIDELIO.UseGC | Enables or disables the use of "Guest Change (GC)" records. | ON/OFF | None | ON |
FIDELIO.UseLinkCheck | If enabled, the BMS server sends an "LS" record for keep alive checking in a cyclic interval. The interval can be defined by FIDELIO.AliveInterval. | ON/OFF | None | OFF |
FIDELIO.UseLALinkCheck | Use "LA" keep alive checking;T;If enabled, the BMS server sends an "LA" record for keep alive checking in a cyclic interval. The interval can be defined by FIDELIO.AliveInterval. | ON/OFF | None | ON |
FIDELIO.AliveInterval | Specifies the interval in seconds for keep alive checking. | 1 - 65535 | seconds | 300 |
FIDELIO.CommandTimeout | Specifies command timeout in seconds used for start up and acknowledged transmission. | 1 - 65535 | seconds | 3 |
FIDELIO.MessagesEnabled | If enabled, messages to and from Fidelio/Opera can be sent or received. | ON/OFF | None | ON |
FIDELIO.RoomStatusEnabled | If enabled, it is request to use RE (room equipment) records. | ON/OFF | None | ON |
FIDELIO.UsedGIRecords | Specifies which optional fields shall be sent by Fidelio/Opera within GI records. Use <NONE> if no additional optional fields shall be sent. | string | None | GAGDGFGLGNGTGVNPSFDATI |
FIDELIO.UsedGCRecords | Specifies which optional fields shall be sent by Fidelio/Opera within GC records. Use <NONE> if no additional optional fields shall be sent. | string | None | ROGAGDGFGLGNGTGVNPDATI |
FIDELIO.UsedGORecords | Specifies which optional fields shall be sent by Fidelio/Opera within GO records. Use <NONE> if no additional optional fields shall be sent. | string | None | SFDATI |
FIDELIO.UsedRERecords | Specifies which optional fields shall be sent by Fidelio/Opera within RE records. Use <NONE> if no additional optional fields shall be sent. | string | None | G#CSDNRSCTVMPPML |
SYS.SihotExtension | Enable Sihot extension. | ON/OFF | None | OFF |
, multiple selections available,
Related content
Integrate Fidelio/Opera
Integrate Fidelio/Opera
Read with this
HTTP driver configuration
HTTP driver configuration
More like this
System Configuration
System Configuration
More like this
Messenger Module
Messenger Module
More like this
SYSTEM Parameters
SYSTEM Parameters
More like this
MQTT broker definitions
MQTT broker definitions
More like this