OPC.GroupAddressType: 3Level -> ITEM ID = "NETx\XIO\KNX\192.168.1.1\00/2/001"

 


Parameter

OPC.PrefixedItemID

Description

It defines whether the leading "0"-characters shall be added to server item IDs. ON - defines that leading "0"characters are added to the item IDs of KNX group addresses OFF - defines that the item IDs of KNX group addresses do not contain leading "0"-characters

Scope

ON, OFF

Unit

None

Default value

ON

...


Info
!Attention: This parameter has crucial influence on the structure of all server item IDs.

...

OPC.PrefixedItemID: ON -> ITEM ID = "NETx\XIO\KNX\192.168.1.1\00/2/001"
OPC.PrefixedItemID: OFF -> ITEM ID = "NETx\XIO\KNX\192.168.1.1\0/2/1" 


Parameter

OPC.AsyncTimeout

Description

It defines the timeout value for asynchronous OPC queries. If no answer to an OPC query is received within this time interval, the quality of all queried datapoints will be set to UNCERTAIN.

Scope

1 - 60

Unit

seconds

Default value

5

...

Info

!Attention: If the parameter is set on "ON", each OPC "WRITE" command will result in sending up telegrams to the field network. In the case of KNX, up to three KNX telegrams are sent.

...



Parameter

OPC.RefreshOnEqualValue

Description

It specifies whether OPC "OnDataChange" events are generated by incoming values from the field level even if the values are unchanged. ON - the "OnDataChange" of events will be generated OFF - the "OnDataChange" of events will be generated only with changes of value

Scope

ON, OFF

Unit

None

Default value

ON

 


Example:
If the server receives two KNX telegrams with same value and same address (IP + KNX group address) and the option "OPC.RefreshOnEqualValue" is set to "OFF", the OPC "OnDataChange" event is generated only for the first telegram, since the second telegram does not cause a change of value of the datapoint. If this option is set on "ON", then two OPC "OnDataChange" events are generated.
 

...

Info

!Attention: Use the following option only with caution! 



Parameter

OPC.AllValuesValid

Description

If set to "'ON"', server items always have the quality "'GOOD"', even if their quality is "'BAD"' or "'UNCERTAIN"'. This option can be used for limited OPC clients that are not aware of OPC qualities other than "'GOOD"'.

Scope

ON, OFF

Unit

None

Default value

OFF