Skip to end of metadata
Go to start of metadata

You are viewing an old version of this page. View the current version.

Compare with Current View Page History

« Previous Version 16 Next »

Parameter

OPC.GroupAddressType

Description

It defines the format that is used to map KNX group addresses to server item IDs. 2Level - uses the two-level KNX group address format 3Level - uses the three-level KNX group address format

Scope

2level, 3level

Unit

None

Default value

3level

In contrast to defined parameter within the studio, this has a crucial influence on the structure of all server item IDs.

OPC.GroupAddressType: 2Level -> ITEM ID = "NETx\XIO\KNX\192.168.1.1\00/0513"The following examples represent the same KNX datapoint:

OPC.GroupAddressType: 3Level -> ITEM ID = "NETx\XIO\KNX\192.168.1.1\00/2/001"

 

Parameter

OPC.PrefixedItemID

Description

It defines whether the leading "0"-characters shall be added to server item IDs. ON - defines that leading "0"characters are added to the item IDs of KNX group addresses OFF - defines that the item IDs of KNX group addresses do not contain leading "0"-characters

Scope

ON, OFF

Unit

None

Default value

ON

 

!Attention: This parameter has crucial influence on the structure of all server item IDs.


The following examples represent the same KNX datapoint:

OPC.PrefixedItemID: ON -> ITEM ID = "NETx\XIO\KNX\192.168.1.1\00/2/001"
OPC.PrefixedItemID: OFF -> ITEM ID = "NETx\XIO\KNX\192.168.1.1\0/2/1"

 

Parameter

OPC.AsyncTimeout

Description

It defines the timeout value for asynchronous OPC queries. If no answer to an OPC query is received within this time interval, the quality of all queried datapoints will be set to UNCERTAIN.

Scope

1 - 60

Unit

seconds

Default value

5

Parameter

OPC.AsyncReadFromDevice

Description

It specifies whether the response data of the asynchronous OPC value read queries ("READ") shall be read from the server's data base, or whether it shall directly be retrieved from the field device. ON - the field devices are queried OFF - the values are read from the server's data base

Scope

ON, OFF

Unit

None

Default value

OFF

Parameter

OPC.AsyncRefreshFromDevice

Description

It specifies whether the response data of the asynchronous OPC value refresh queries ("REFRESH") shall be read from the server's data base, or whether it shall directly be retrieved from the field device. ON - the field devices are queried OFF - the values are read from the server's data base

Scope

ON, OFF

Unit

None

Default value

OFF

Parameter

OPC.ShowETSStructure

Description

It specifies whether to show an ETS like structure within the server item tree ON - shows the ETS like structure OFF - shows the NXA like structure

Scope

ON, OFF

Unit

None

Default value

OFF

Parameter

OPC.QualityForValueNotSet

Description

It specifies which OPC Quality value shall be used for item values that are not yet set.

Scope

UNCERTAIN, BAD, NOT_CONNECTED

Unit

None

Default value

UNCERTAIN

Parameter

OPC.Delimiter

Description

It specifies which delimiter shall be used for the item IDs within the server item tree.

Scope

String (" not allowed)

Unit

None

Default value

\



!Attention: If the parameter is set on "ON", each OPC "WRITE" command will result in sending up telegrams to the field network. In the case of KNX, up to three KNX telegrams are sent.


 

Parameter

OPC.RefreshOnEqualValue

Description

It specifies whether OPC "OnDataChange" events are generated by incoming values from the field level even if the values are unchanged. ON - the "OnDataChange" of events will be generated OFF - the "OnDataChange" of events will be generated only with changes of value

Scope

ON, OFF

Unit

None

Default value

ON

 

Example:
If the server receives two KNX telegrams with same value and same address (IP + KNX group address) and the option "OPC.RefreshOnEqualValue" is set to "OFF", the OPC "OnDataChange" event is generated only for the first telegram, since the second telegram does not cause a change of value of the datapoint. If this option is set on "ON", then two OPC "OnDataChange" events are generated.
 


!Attention: Use the following option only with caution!

 


Parameter

OPC.AllValuesValid

Description

If set to "'ON"', server items always have the quality "'GOOD"', even if their quality is "'BAD"' or "'UNCERTAIN"'. This option can be used for limited OPC clients that are not aware of OPC qualities other than "'GOOD"'.

Scope

ON, OFF

Unit

None

Default value

OFF

  • No labels