parameter | type | optional/mandatory | description | default |
---|
Name | string | M | Name of the Dali gateway that is used within the gateway definition. |
|
Path | string | O | Path of the Dali gateway that is used within the gateway definition. | not used |
DeviceId | number | M | The DALI number of the device (starting with 1). |
|
Start Test | ItemId | M | Item that is used to start an emergency test. gateway types | description |
---|
Gira/Insta DALI Gateway Plus REG 218000 | , Hager Hager Dali gateway KNX TYA670D | , Jung KNX DALI-Gateway Plus 2098 REGHE | KNX Object #433 + (device ID -1) * 17 (i.e. #433, #450, #467, ...) | Ipas DaliControl e64 | , MDT MDT DaliControl IP Gateway SCN-DALI64.02 | , Merten KNX DALI-Gateway REG-K/1/16(64)/64/IP1 (MEG6725-0001) | , Schneider KNX DALI-Gateway MTN6725-0001 | KNX Object #176 + (device ID -1) * 11 (i.e. #176, #187, ...) | Siemens KNX/DALI Gateway N 141/03, N 141/21, N 141/31 | - Channel A: KNX Object #607 + (device ID -1) * 2 (i.e. #607, #609, ...)
- Channel B: KNX Object #1306 + (device ID -1) * 2 (i.e. #1306, #1308, ...)
|
|
|
Test Result | ItemId | M | Item that provides the test result. Dependening on the gateway type, the following KNX communication objects have to be used: gateway types | description |
---|
Gira/Insta DALI Gateway Plus REG 218000 | , Hager Hager Dali gateway KNX TYA670D | , Jung KNX DALI-Gateway Plus 2098 REGHE | KNX Object #432 + (device ID -1) * 17 (i.e. #432, #449, #466, ...) | Ipas DaliControl e64 | , MDT MDT DaliControl IP Gateway SCN-DALI64.02 | , Merten KNX DALI-Gateway REG-K/1/16(64)/64/IP1 (MEG6725-0001) | , Schneider KNX DALI-Gateway MTN6725-0001 | KNX Object #177 + (device ID -1) * 11 (i.e. #177, #188, ...) | Siemens KNX/DALI Gateway N 141/03, N 141/21, N 141/31 | - Channel A: KNX Object #608 + (device ID -1) * 2 (i.e. #608, #610, ...)
- Channel B: KNX Object #1307+ (device ID -1) * 2 (i.e. #1307, #1309, ...)
|
|
|