Basic architecture
The NETx BMS Server provides an interface which can be used to integrate information from the hotel management system MICROS Oracle Fidelio/Opera. Using this interface, information about the check-in/check-out procedure, the hotel guests and the hotel room states can be retrieved. In addition, it is also possible to send dedicated information from the NETx BMS Server to the MICROS Oracle Fidelio/Opera system. This interface for the NETx BMS Server is certified by MICROSOracle. The official certificate can be found here.
The following figure shows how the integration has to be done.
In order to connect to MICROS Oracle Fidelio/Opera system, the so called IFC interface from MICROS Oracle Fidelio/Opera has to be activated at the MICROS Oracle Fidelio/Opera side. This has to be done by the MICROS Oracle Fidelio/Opera integrator. The following figure shows a screenshot of the IFC logging window:
...
The communication between the IFC interface and the NETx BMS Server is based on TCP/IP. In detail, the IFC interface acts as a TCP server and the NETx BMS Server acts a TCP client. The protocol itself is based on a communication standard called FIAS.
...
Info |
---|
The MICROS Fidelio/Opera interface is already included in the setup of the NETx BMS Server. In order to use it, an extra license is needed – for testing purposes, the "Demo" license includes the MICROS Oracle Fidelio/Opera interface. Please contact the team of NETxAutomation for more information. |
...
After having defined all rooms, the NETx BMS Server has to be restarted. Afterwards, the configured devices are shown within the item tree under the sub tree "NETx\API\NXA_FIDELIO".
...
- BuildingNumber
- String, read only
- Specified within Room Definitions within NETx BMS Server
- LevelNumber
- String, read only
- Specified within Room Definitions within NETx BMS Server
- RoomNumber
- String, read only
- Specified within Room Definitions within NETx BMS Server. Must be identifcally identically with the room number used within Fidelio/Opera
- Description
- String, read only
- Specified within Room Definitions within NETx BMS Server
- GuestsCount
- UINT8, read only
- Amount of guest that are checked in for this room
- GuestName
- String, read only
- Guest name that is received from Fidelio/Opera
- GuestLanguage
- String, read only
- Language code that is received from Fidelio/Opera. E.g. de, en, es, ...
- GuestVIP
- UINT8, read only
- VIP status that is received from Fidelio/Opera
- RoomChecked
- Boolean, read only
- True if at least 1 guest is check in this room – False if room is free
- ClassOfService (read only)
- UINT8, read only
- Received from Fidelio/Opera. 0 (Barred/hotel internal only), 1 (local), 2 (national), 3 (no restrictions)
- DoNotDisturb
- Boolean, read only
- True if DND is received from Fidelio/Opera – False otherwise
- RoomStatus
- UINT8, read and writable
- See table below
- ClearText
- String, read and writable
- GuestArrivalDate
- DateTime, read only
- Arrival data and time of guest. Normally this is equal to the checkin data and time. Please keep in mind that Fidelio/Opera is not providing an arrival date before the checkin signal
- GuestDepartureDate
- DateTime, read only
- Scheduled depature data and time of guest.
- PrinterPort
- UINT8, read only
- MessageCount
- UINT8, read only
- Amount of messages that are available for this room
- NextMessage
- Boolean, write only
- If set to true, the next message that is queued within the NETx BMS Server server is shown within the server item "MessageText"
- MessageText
- String, read only
- Last message that was received from Fidelio/Opera
- GetMessage
- Boolean, write only
- If set to true, all available messages are fetched from Fidelio/Opera and stored within the NETx BMS Serverserver. Using the item "NextMessage", these messages can be shown within the item "MessageText"
- SendMessage
- String, read and writable
- Used to send a message to Fidelio/Opera for this room
- MessageLightStatus
- Boolean, write only
Note that this list of data points is fixed by MICROS Fidelio/Opera – not by the NETx BMS Serverserver.
The room status is a very important information which can also be changed from the NETx BMS Server server side. Fidelio/Opera specifies the following predefined values:
Code | Room status |
---|---|
1 | Dirty/Vacant |
2 | Dirty/Occupied |
3 | Clean/Vacant |
4 | Clean/Occupied |
5 | Inspected/Vacant |
6 | Inspected/Occupied |
These are the predefined room states that are available within Fidelio/Opera. However, it is possible to specify additional room states for additional functionality. For example, further states for "Do not disturb" or "Make up room" can be defined. Using this additional room states, it is possible to send additional information from the BMS to the Fidelio/Opera system. A typical use case is to add a KNX switch for DND that sends a user-defined room status (e.g. 7 "DND) to the Fidelio/Opera system. These additional room states have to configured within Fieldio/Opera by the Fidelio/Opera integrator.
...
After having configured the Fidelio/Opera interface, the provided data points can be linked to other data points within the NETx BMS Serverserver. You can use V-Links, Server Tasks, LUA script or XLogic commands for providing this functionality.
A typical use case would be the mapping of the RoomCheck item from Fidelio/Opera to a data point like the setpoint set point or the mode of the room's climate control. For implementing this use case, a predefined XLogic command called "HotelCheckInCheckOut" is already included within the NETx BMS Serverserver. Open the XCommand Event Definitions (BMS Studio --> Extensions) and add a new definition line. Give the logic a name (e.g. Room101), select "ON_INPUT" as type and select the XLogic "HotelCheckInCheckOut". Within the configuration dialog, select the input item (e.g. NETx\API\NXA_FIDELIO\PartA\Floor1\101\RoomChecked) and as output the data point that shall be controlled by the checkin/checkout signal (e.g. KNX group address of the setpoint set point of the room). The following screenshot shows an example:
...
Repeat these steps for a hotel rooms. After having finished all definitions, restart the NETx BMS Serverserver.
Info |
---|
To add additional definitions in a more easier and faster way, you can use the export/import to MS Excel function of the definition table. |
Article applies to the following products:
- NETx BMS Platform
- NETx Multi Protocol Server
- NETx BMS Server 2.0