...
Within this configuration file, general settings for the Fidelio
...
/Opera interface are configured.
Info | ||
---|---|---|
| ||
<WorkspaceDirectory>\ConfigFiles\ |
...
nxapiFidelio.cfg |
...
...
- FIDELIO
- SYS
FIDELIO-Parameters
...
Parameter | Description | Scope | Unit | Default value |
---|---|---|---|---|
FIDELIO.IPAddress | Specifies the IP address of the Fidelio/Opera server. | IP address | None | None |
FIDELIO.Port | Specifies the TCP port number of the Fidelio/Opera server. | 1-65535 | None | 5003 |
FIDELIO.LRC | Turns LRC for data telegrams on or off. | ON/OFF | None | OFF |
SYS.RefreshInterval | Defines the time between two calls for data to the Fidelio/Opera server. | numeric | seconds | 20 |
FIDELIO.Logging | Enables logging of data telegrams to and from the Fidelio/Opera server. | ON/OFF | None | OFF |
FIDELIO.UpdateOnReconnect | If set, when the connection to the Fidelio/Opera server is (re-)established data from Fidelio/Opera server are queried to update the information in the NETx BMS Core Server. | ON/OFF | None | ON |
FIDELIO.UseControlByte | Enables the acknowledged transmission of data telegrams. | ON/OFF | None | OFF |
FIDELIO.UseGC | Enables or disables the use of "Guest Change (GC)" records. | ON/OFF | None | ON |
FIDELIO.UseLinkCheck | If enabled, the BMS server sends an "LS" record for keep alive checking in a cyclic interval. The interval can be defined by FIDELIO.AliveInterval. | ON/OFF | None | OFF |
FIDELIO.UseLALinkCheck | Use "LA" keep alive checking;T;If enabled, the BMS server sends an "LA" record for keep alive checking in a cyclic interval. The interval can be defined by FIDELIO.AliveInterval. | ON/OFF | None | ON |
FIDELIO.AliveInterval |
Specifies the interval in seconds for keep alive checking. | 1 - 65535 | seconds | 300 |
FIDELIO.CommandTimeout |
Specifies command timeout in seconds used for start up and acknowledged transmission. | 1 - 65535 | seconds | 3 | |
FIDELIO.MessagesEnabled | If enabled, messages to and from Fidelio/Opera can be sent or received. | ON/OFF | None | ON |
FIDELIO.RoomStatusEnabled | If enabled, it is request to use RE (room equipment) records. | ON/OFF | None | ON |
FIDELIO.UsedGIRecords |
Specifies which optional fields shall be sent by Fidelio/Opera within GI records. Use <NONE> if no additional optional fields shall be sent. | string | None | GAGDGFGLGNGTGVNPSFDATI |
FIDELIO.UsedGCRecords |
Specifies which optional fields shall be sent by Fidelio/Opera within GC records. Use <NONE> if no additional optional fields shall be sent. | string | None | ROGAGDGFGLGNGTGVNPDATI |
FIDELIO.UsedGORecords |
Specifies which optional fields shall be sent by Fidelio/Opera within GO records. Use <NONE> if no additional optional fields shall be sent. | string | None | SFDATI |
FIDELIO.UsedRERecords |
Specifies which optional fields shall be sent by Fidelio/Opera within RE records. Use <NONE> if no additional optional fields shall be sent. | string | None | G#CSDNRSCTVMPPML |
...
SYSTEM-Parameters
...
Default value
...
Defines the time between two calls for data to the Fidelio/Opera server.
...
SYS.SihotExtension | Enable Sihot extension. | ON/OFF | None | OFF |