Some gateways do not have a global KNX communication object for starting an emergency test and for getting the result – they have a separate object for each device. Therefore, the ItemIDs has to be configured for each emergency lighting separately.

This is done in the Emergency Test Mapping Defintions Table:The information provided in this table is required for the LaMPS module to execute emergency tests of DALI devices.

There are 2 basic ways how KNX/DALI gateways handle communication objects for DALI device emergency testing:

  • Case 1: Communication objects exist per DALI device. The respective group addresses have to be provided for each DALI device.
    This applies to the following gateway types:

    • Gira/Insta DALI Gateway Plus REG 218000

    • Hager Dali gateway KNX TYA670D

    • Jung KNX DALI-Gateway Plus 2098 REGHE

    • Ipas DaliControl

    • MDT DaliControl IP Gateway

    • Merten KNX DALI-Gateway

    • Schneider KNX DALI-Gateway

    • Siemens KNX/DALI Gateway N 141/03, N 141/21, N 141/31
    • Siemens KNX/DALI Gateway N 141/02
  • Case 2: Communication objects exist per DALI line. That is, LaMPS will address the DALI devices on writing. The required group addresses have already been provided in the gateway configuration. In order to treat DALI devices as emergency lights, they have to be mentioned in this table.

    Info

    If there is no mentioning of a given gateway in this table, then all its devices will be treated as emergency lights.

    This applies to all KNX/DALI gateways that are not listed in case 1.


number
parametertypeoptional/mandatorydescriptiondefault
NamestringMName of the Dali gateway that is used within the gateway definition.
PathstringOPath of the Dali gateway that is used within the gateway definition.not used
DeviceId
Devicesdevice (case 1) or device range (case 2)M
The DALI number of the device (starting with 1).

Case 1: The number of a single DALI device.

Case 2: A list of DALI devices or device ranges is allowed, e.g.

  • 1
  • 1,2,5,6
  • 1-10,12,15-22

Start TestItemIdM for case 1 devices

Item that is used to start an emergency test.

gateway typesdescription

Gira/Insta DALI Gateway Plus REG 218000

Hager Dali gateway KNX TYA670D

Jung KNX DALI-Gateway Plus 2098 REGHE

KNX Object #433 + (device ID -1) * 17 (i.e. #433, #450, #467, ...)

Ipas DaliControl

e64

MDT DaliControl IP Gateway

SCN-DALI64.02

Merten KNX DALI-Gateway

REG-K/1/16(64)/64/IP1 (MEG6725-0001)

Schneider KNX DALI-Gateway

MTN6725-0001KNX Object #176 + (device ID -1) * 11 (i.e. #176, #187, ...)

See here.
Siemens KNX/DALI Gateway N 141/03, N 141/21, N 141/31
  • Channel A:
    • App version < 5: KNX Object #607 + (device ID -1) * 2 (i.e. #607, #609, ...)
    • App version >= 5: KNX Object #690+ (device ID -1) * 2 (i.e. #690, #691, ...)
  • Channel B:
    • App version < 5: KNX Object #1306 + (device ID -1) * 2 (i.e. #1306, #1308, ...)
    • App version >= 5: KNX Object #1472 + (device ID -1) * 2 (i.e. #1472, #1473, ...)
Siemens KNX/DALI Gateway N 141/02KNX Object #146 + (device ID -1) * 8 (i.e. #146, #154, ...)



Test ResultItemIdM for case 1 devices

Item that provides the test result. Dependening on the gateway type, the following KNX communication objects have to be used:

gateway typesdescription

Gira/Insta DALI Gateway Plus REG 218000

Hager Dali gateway KNX TYA670D

Jung KNX DALI-Gateway Plus 2098 REGHE

KNX Object #432 + (device ID -1) * 17 (i.e. #432, #449, #466, ...)

Ipas DaliControl

e64

MDT DaliControl IP Gateway

SCN-DALI64.02

Merten KNX DALI-Gateway

REG-K/1/16(64)/64/IP1 (MEG6725-0001)

Schneider KNX DALI-Gateway

MTN6725-0001KNX Object #177 + (device ID -1) * 11 (i.e. #177, #188, ...)

See here.
Siemens KNX/DALI Gateway N 141/03, N 141/21, N 141/31
  • Channel A:
    • App version < 5: KNX Object #608 + (device ID -1) * 2 (i.e. #608, #610, ...)
    • App version >= 5: KNX Object #691 + (device ID -1) * 2 (i.e. #691, #693, ...)
  • Channel B:
    • App version < 5: KNX Object #1307+ (device ID -1) * 2 (i.e. #1307, #1309, ...)
    • App version >= 5: KNX Object #1473+ (device ID -1) * 2 (i.e. #1473, #1475, ...)
Siemens KNX/DALI Gateway N 141/02KNX Object #147 + (device ID -1) * 8 (i.e. #147, #155, ...)