Within this configuration file, general settings for the Fidelio

...

/Opera interface are configured.

Info
titleFile location

<WorkspaceDirectory>\ConfigFiles\

...

Within this configuration, all Fidelio settings are specified. Each parameter is identified with a name. The name is case-insensitive (i.e. capitalization is not considered). The scope indicates the allowed values of the parameter. The default value specifies the values that is used when no value is set by the user.

The parameters which can be defined in this file are divided into the following two groups:

  • FIDELIO
  • SYS

...

nxapiFidelio.cfg


 

 

...

ParameterDescriptionScopeUnit

Default value

FIDELIO.IPAddressSpecifies the IP address of the Fidelio/Opera server.IP addressNoneNone
FIDELIO.PortSpecifies the TCP port number of the Fidelio/Opera server.1-65535None5003
FIDELIO.LRCTurns LRC for data telegrams on or off.ON/OFFNoneOFF
SYS.RefreshIntervalDefines the time between two calls for data to the Fidelio/Opera server.numericseconds20
FIDELIO.LoggingEnables logging of data telegrams to and from the Fidelio/Opera server.ON/OFFNoneOFF
FIDELIO.UpdateOnReconnectIf set, when the connection to the Fidelio/Opera server is (re-)established data from Fidelio/Opera server are queried to update the information in the NETx BMS Core Server.ON/OFFNone

ON

FIDELIO.UseControlByteEnables the acknowledged transmission of data telegrams.ON/OFFNoneOFF
FIDELIO.UseGCEnables or disables the use of "Guest Change (GC)" records.ON/OFFNone

ON

FIDELIO.UseLinkCheckIf enabled, the BMS server sends an "LS" record for keep alive checking in a cyclic interval. The interval can be defined by FIDELIO.AliveInterval.ON/OFFNoneOFF
FIDELIO.UseLALinkCheckUse "LA" keep alive checking;T;If enabled, the BMS server sends an "LA" record for keep alive checking in a cyclic interval. The interval can be defined by FIDELIO.AliveInterval.ON/OFFNone

ON

FIDELIO.AliveIntervalSpecifies the interval in seconds for keep alive checking.1 - 65535seconds300
FIDELIO.CommandTimeoutSpecifies command timeout in seconds used for start up and acknowledged transmission.1 - 65535seconds3
FIDELIO.MessagesEnabledIf enabled, messages to and from Fidelio/Opera can be sent or received.ON/OFFNone

ON

FIDELIO.RoomStatusEnabledIf enabled, it is request to use RE (room equipment) records.ON/OFFNone

ON

FIDELIO.UsedGIRecordsSpecifies which optional fields shall be sent by Fidelio/Opera within GI records. Use <NONE> if no additional optional fields shall be sent.stringNoneGAGDGFGLGNGTGVNPSFDATI
FIDELIO.UsedGCRecordsSpecifies which optional fields shall be sent by Fidelio/Opera within GC records. Use <NONE> if no additional optional fields shall be sent.stringNoneROGAGDGFGLGNGTGVNPDATI
FIDELIO.UsedGORecordsSpecifies which optional fields shall be sent by Fidelio/Opera within GO records. Use <NONE> if no additional optional fields shall be sent.stringNoneSFDATI
FIDELIO.UsedRERecordsSpecifies which optional fields shall be sent by Fidelio/Opera within RE records. Use <NONE> if no additional optional fields shall be sent.stringNoneG#CSDNRSCTVMPPML

...

SYSTEM-Parameters

...

Default value

...

Defines the time between two calls for data to the Fidelio/Opera server.

...

SYS.SihotExtensionEnable Sihot extension.ON/OFFNoneOFF