Basic architecture

The NETx Server provides an interface which can be used to integrate information from the hotel management system Oracle Fidelio/Opera. Using this interface, information about the check-in/check-out procedure, the hotel guests and the hotel room states can be retrieved. In addition, it is also possible to send dedicated information from the NETx Server to the Oracle Fidelio/Opera system. This interface for the NETx Server is certified by Oracle. The official certificate can be found here.

The following figure shows how the integration has to be done.

Image RemovedImage Added

In order to connect to Oracle Fidelio/Opera system, the so called IFC interface from Oracle Fidelio/Opera has to be activated at the Oracle Fidelio/Opera side. This has to be done by the Oracle Fidelio/Opera integrator. The following figure shows a screenshot of the IFC logging window:

...

Info

FIAS is a common protocol for interfacing with hotel management system. Many other vendors for hotel management system are also using FIAS. If you have to integrate a hotel management system other the than supported ones, please contact the team of NETxAutomation.

Installation

Info

 In order to use the Fidelio/Opera interface, an extra license is needed – for testing purposes, the "Demo" license includes the Oracle Fidelio/Opera interface.  Please contact the team of NETxAutomation for more information.

...

After having installed the interface, restart the server.

Integration steps

To start, open the BMS Core Studio. First, Open Modules > Fidelio/Opera > Driver configuration and configure the IP address and port number that you have enter entered within the web service URL. This can be done by selecting "Driver Configuration" within the menu "Modules" -> "Fidelio/Opera". If this information is not known, please ask the Fidelio/Opera integrator.

...

The retrieved information from Fidelio/Opera is stored as Server Items. Here all available Server Items that are available for each room are listed (including their access rights):

Item nameData typeAccessNotes
BuildingNumberString

...

read only

Specified within Room Definitions within NETx Server

LevelNumberString

...

read only

Specified within Room Definitions within NETx Server

RoomNumberString

...

read only

Specified within Room Definitions within NETx Server. Must be

...

identical with the room number used within Fidelio/Opera

DescriptionString

...

read only

Specified within Room Definitions within NETx Server

GuestsCountUINT8

...

read only

...

Number of guest that are checked in for this room

GuestNameString

...

read only

Guest name that is received from Fidelio/Opera

GuestLanguageString

...

read only

Language code that is received from Fidelio/Opera. E.g. de, en, es, ...

GuestVIPUINT8

...

read only

VIP status that is received from Fidelio/Opera

GuestIdStringread onlyReservation / guest ID
RoomCheckedBoolean

...

read only

True if at least 1 guest is check in this room – False if room is free

...

RoomCheckedForecastBooleanread onlyTrue if forecast check-in happens. Only available if Sihot extension is enabled.
ClassOfServiceUINT8read only

Received from Fidelio/Opera. 0 (Barred/hotel internal only), 1 (local), 2 (national), 3 (no restrictions)

DoNotDisturb Boolean

...

read only

True if DND is received from Fidelio/Opera – False otherwise

RoomStatusUINT8

...

read and writable

See table below

ClearTextString

...

read and writable
GuestArrivalDate

DateTime

...

read only

Arrival data and time of guest. Normally, this is equal to the

...

check-in data and time. Please keep in mind that Fidelio/Opera is not providing an arrival date before the

...

check-in signal

GuestDepartureDate

DateTime

...

read only

Scheduled depature data and time of guest.

PrinterPortUINT8

...

read only
MessageCountUINT8

...

read only

...

Number of messages that are available for this room
NextMessageBoolean

...

write only

If set to true, the next message that is queued within the server is shown within the server item "MessageText"

MessageTextString

...

read only

...


GetMessage Boolean

...

write only

If set to true, all available messages are fetched from Fidelio/Opera and stored within the server. Using the item "NextMessage", these messages can be shown within the item "MessageText"

SendMessage String

...

read and writable

Used to send a message to Fidelio/Opera for this room

MessageLightStatusBoolean

...

write only

Note that this list of data points is fixed by MICROS Fidelio/Opera – not by the server.

...

These are the predefined room states that are available within Fidelio/Opera. However, it is possible to specify additional room states for additional functionality. For example, further states for "Do not disturb" or "Make up room" can be defined. Using this additional room states, it is possible  to send additional information from the BMS to the Fidelio/Opera system. A typical use case is to add a KNX switch for DND that sends a user-defined room status (e.g. 7 "DND) to the Fidelio/Opera system. These additional room states have to configured within Fieldio/Opera by the Fidelio/Opera integrator.

Adding control functionality

After having configured the Fidelio/Opera interface, the provided data points can be linked to other data points within the server. You can use V-Links, Server Tasks, LUA script or XLogic commands for providing this functionality.

...

Info

To add additional definitions in a more easier and faster way, you can use the export/import to MS Excel function of the definition table.