The configuration of the main/backup functionality is done in the Main/Backup configuration file.
File location
<WorkspaceDirectory>\ConfigFiles\nxaXLink.40.cfg
Parameter | Description | Scope | Unit | Default value |
---|---|---|---|---|
XLINK.Redundancy | If ON, the main/backup functionality will be activated. | ON, OFF | None | OFF |
XLINK.MainServerIPAddress | The IP address of the main server's network interface. | IP address | None | None |
XLINK.BackupServerIPAddress | The IP address of the backup server's network interface. | IP address | None | None |
XLINK.MainServerPort | TCP port for secure connection to main server | 1 – 65535 | None | 14732 |
XLINK.Password | TLS connection password for second server | String | None | None |
XLINK.PIN | TLS connection PIN of this server. | String | None | None |
XLINK.ConnectionTimeout | Specifies the timeout for a detecting a lost connection to the second server. If the second server does not response within the given time interval, it will assume that the second server is down. | 1 – 600 | s | 10 |
XLINK.CommandTimeout | Specifies the timeout in seconds of VNET commands between main and backup server. | 1 – 10000 | s | 30 |
Article applies to the following products:
- NETx BMS Platform
- NETx Multi Protocol Server