The configuration of the main/backup functionality is done in the Main/Backup configuration file.

File location

<WorkspaceDirectory>\ConfigFiles\nxaXLink.40.cfg


ParameterDescriptionScopeUnitDefault value
XLINK.RedundancyIf ON, the main/backup functionality will be activated.ON, OFFNoneOFF
XLINK.MainServerIPAddress

The IP address of the main server's network interface.

IP addressNoneNone
XLINK.BackupServerIPAddressThe IP address of the backup server's network interface.IP addressNoneNone
XLINK.MainServerPortTCP port for secure connection to main server1 – 65535None14732
XLINK.PasswordTLS connection password for second serverStringNoneNone
XLINK.PINTLS connection PIN of this server.StringNoneNone
XLINK.ConnectionTimeoutSpecifies the timeout for a detecting a lost connection to the second server. If the second server does not response within the given time interval, it will assume that the second server is down.1 – 600s

10

XLINK.CommandTimeoutSpecifies the timeout in seconds of VNET commands between main and backup server.1 – 10000s30

Article applies to the following products:

  • NETx BMS Platform
  • NETx Multi Protocol Server


 