Skip to end of metadata
Go to start of metadata

You are viewing an old version of this page. View the current version.

Compare with Current View Page History

Version 1 Next »

Update on Reconnect

Normally, Fidelio/Opera is only sending new checkins/checkouts – the current state of all rooms is not sent after connecting to Fidelio/Opera.

 

However, there is a possibility to initiate a database resync of Fidelio/Opera after connecting to it. First, you have to activate “Enable Update on Reconnect” within the configuration of our BMS server. This is done in the BMS Studio via “Modules” à “Fidelio/Opera” -> “Driver Configuration …”. Please find enclosed a screenshot (Fidelio_Update.png).

 

Then you have to active the resync option within the Fidelio/Opera Interface (called IFC) – otherwise Fidelio/Opera will ignore resync requests from our BMS Server. To activate this option, you have to change the configuration of the IFC. This can be done by the Fidelio integrator or if you have access to the configuration of the Fidelio Interface, you can enable it. Please find attached a screenshot where you can find how you can enable it (Fidelio_Datasync.png). You have to set the DataResyncOption to 0 (XML Configuration -> IFC1 -> Application Layer --> FIAS).

  • No labels