Location:
<WorkspaceDirectory>\DataFiles\xio.BACnet.PropertyDefinitions.dat
The BACnet interface allows to map BACnet properties to server items.
The structure of the BACnet property definition file is as follows:
' BACnet property configuration file
' Device Name Filter;Object Name Filter;Property ID;Access rights [R];Polling interval (ms) [object-setting]
;Input;out-of-service;RW;5000
;;description;R;
Each line - except comment lines that start with ' - defines a filter rule for BACnet Objects. For each BACnet object matching that rule the respective property item is created in the server if applicable to the object.
<tr> <td>1</td> <td>Device Name Filter</td> <td></td> <td> The BACnet Device Name
Filter. Wildcards are allowed. </td> </tr>
<tr> <td>2</td> <td>Object Name Filter</td> <td></td> <td> The BACnet Object Name
Filter. Wildcards are allowed. </td> </tr>
<tr> <td>3</td> <td>Property ID</td> <td></td> <td> This attribute defines the BACnet Property. </td> </tr>
<tr> <td>4</td> <td>Access rights</td> <td></td> <td> Specifies permissions of the BACnet property in the NETx BMS Core Server. Possible values are R (read-only; default), RW (read-write), and W (writeonly). This permission cannot supersede the permission configured in the device. </td> </tr>
<tr> <td>5</td> <td>Polling interval</td> <td></td> <td> Specifies the polling interval for the resulting porperty items. Default polling interval is used as of the corresponding BACnet object. </td>
</tr>