Skip to end of metadata
Go to start of metadata

You are viewing an old version of this page. View the current version.

Compare with Current View Page History

« Previous Version 5 Next »

Location:
<WorkspaceDirectory>\DataFiles\nxaGatewayDefinitions.35.dat


The gateway manager maintains the connections to the KNXnet/IP devices which are connected to the KNX system. The gateway definition table defines all the KNXnet/IP interfaces and routers that are used within the project.

! No telegrams are sent to the offline gateways.

The structure of the gateway definition file is as follows:

'Syntax of the Gateway Definition Table:
'IP Address;Type;Port;Name;Locality;Description ;Options'
192.168.1.1;IGS;51000; GATE 1;Room 51;pre-defined Gateway 1
192.168.1.2;NETIP;3671;Gate2;;;;;;;
192.168.1.3;EIBNODE;1634;Gate3;;;;;;;


Each line – except comment lines that start with ' – defines a single KNXnet/IP gateway.

! The virtual "BROADCAST" gateway is added by the system and must not be defined in the table.

 

    
1IP Address This attribute specifies the IP address of the KNXnet/IP gateway. The IP address is also used to uniquely identify the gateway within the server. Therefore, it must be unique within the whole network.
2Type The type of the KNXnet/IP gateway. "IGS" refers to ABB IG/S, EIBNODE to b.a.b - technologie eibnode, and NETIP to all other KNXnet/IP routers and interfaces.
3UDP Port This attributes represents the UDP port number which is used to connect to the gateway.
4Name It is used to give the gateway a human-readable name (can be any user-defined string).
5Locality This attribute can be used to specify the location of the gateway (can be any user-defined string).
6Description This attribute can be used to specify a human-readable text that further describes the gateway (can be any user-defined string).
7Options If the gateway is of type "EIBNODE", the SenderNetID has to be specified here.
8 - 11Path, Extended Data 1 - 3 These columns are for internal use only.

 

 

  • No labels