Provides a logical AND function of two or more data points.
Description
This logic implements a logical ANDÂ function of two or more input data points. The input data points and the output data point must be of type boolean.
Inputs
- Input1 (ItemID): 1st operand. Must be of type bool.
- Input2Â (ItemID): 2nd operand. Must be of type bool.
- Input3 (ItemID, optional): 3rd operand. Must be of type bool.
- ...
- Input10 (ItemID, optional): 10th operand. Must be of type bool.
Outputs
- Output (ItemID): Output item. Must be of type bool.
Parameters
- Write to bus (bool, optional): if set to "false", the value is only updated within the NETx BMS Server. If set to true (default value), the value is also forwarded to the field network.
- Verify quality (bool, optional): if set to "true" (default value), the value is not forwarded when the input's quality is not "GOOD".
Possible trigger types
All
Available since:
NETx BMS Server 2.0