Supported gateways

Vendor

Name

Order number

Application

Gira

DALI-Gateway Plus

2180 00

 DALI Gateway C00D11

DALI-Gateway Plus

2180 00

 DALI Gateway C00D12

DALI-Gateway Tunable White Plus

2108 00

 DALI Gateway TW C02011

DALI-Gateway Tunable White Plus

2108 00

 DALI Gateway TW C02012

Hager

KNX-DALI Gateway

TYA670D

DALI Gateway C01711

KNX-DALI Gateway

TYA670D

DALI Gateway C01712

KNX-DALI Gateway

TYA670D

Passerelle DALI C01713

KNX DALI TW GATEWAY

TYA670W

STYA670W EN

KNX DALI TW GATEWAY

TYA670W

STYA670W DE

KNX DALI TW GATEWAY

TYA670W

STYA670W FR

Jung

DALI-Gateway Plus

2098REGHE

DALI Gateway C00D11

DALI-Gateway Plus

2099REGHE

DALI Gateway C00D12

DALI-Gateway TW

2099REGHE

 DALI Gateway TW C02011

DALI-Gateway TW

2099REGHE

DALI Gateway TW C02012

Configuration

In addition to the common configuration options the following configuration options are available for each channel:

parameter

type

optional/mandatory

communication object

description

default

Fault General

ItemId

M

KNX Object #1524, polled

True, if there is an error for at least 1 DALI device.


Fault Short Circuit

ItemId

O

KNX Object #1527

True, if there is a general short cut on the DALI bus.


Fault Power Failure

ItemId

O

KNX Object #1525

True, if there is a power failure on the DALI bus.


Emergency Mode Active

ItemId

O

KNX Object #1541

True, if DALI devices are in emergency mode.


Emergency Lighting Failure

ItemId

O

KNX Object #1542, polled

True, if there is an error for at least 1 emergency DALI device. This config element is optional. If it is not used, emergency lighting test features are not available.


Error per DALI Device

ItemId

M

KNX Object #1544

KNX feedback object for DALI device errors.


Emergency Test Interval

int

O


Specifies how long the driver will wait between sending two emergency start requests.

10 s

In order to use the object "Error per DALI device" within our LaMPS module, it is important to active the following options within the parameters of the device:

The objects Fault General (#1524) and Emergency Lighting Failure (#1542) can be configured as passive or active feedback objects. If at least one of them is set as passive, "Poll Device" should be set to true. 

The objects Fault General (#1524) and Error per DALI Device (#1544) must be linked to a group address. Otherwise the DALI gateway will be considere as "not used" and therefore be ignored for the export.

Since these gateways do not have a global KNX communication object for starting an emergency test and for getting the result (they have a separate object for each device), the ItemIDs have to be configured for each emergency lighting separately. This is done in the Emergency Test Mapping.

If you want to use emergency tests for single battery powered emergency lights, it is of utmost importance to enable the external activate within the ETS parameters of the gateway:

Functional description

This KNX/DALI gateway type provides a single DALI channel with up to 64 DALI devices. In addition to normal DALI testing, emergency lighting and extended tests for emergency lighting are supported, too.

Following Server Items are available:

item name

description

KNX IP Connection

This Item reflects the KNXnet/IP tunneling connection to KNXnet/IP router or interface which is used to communicate with the KNX/DALI gateway.

Fault

True, if there is either a Power Failure, Short Circuit, Lamp, Ballast or Converter fault.

Fault Devices

True, if there is a lamp, ballast or converter failure for at least 1 DALI device. If configured, LaMPS is starting to test all configured devices in order to see which device(s) have a fault.

Fault Lamp

True, if there is a lamp fault of one or more DALI devices.  

Fault Ballast

True, if there is a ballast fault of one or more DALI devices.  

Fault Converter

This item is only available for at least one DALI device that supports emergency lighting. If true, there is a converter fault of one or more DALI devices.

Fault Power Failure

True, if there is a power failure on the DALI bus.

Fault Short Circuit

True, if there is a general short cut on the DALI bus.

Since this gateway type also supports emergency lighting, the LaMPS module distinguishes between a normal DALI test and an emergency DALI test.

Normal DALI testing server items per DALI gateway

item name

access

description

Trigger faulty devices only

RW

If true then the next test will test only devices that are mentioned in the Faulty devices server item. Otherwise all devices are tested.

Trigger Test

W

Used to trigger a normal DALI test for all devices.

Test Running

R

True, when a normal DALI test is currently running.

Number Faulty Devices

R

Number of faulty devices as determined in the last test execution.

Faulty devices

R

A comma-separated sorted list of numbers of faulty DALI devices.


Emergency testing server items per DALI gateway

For DALI emergency testing, the following Server Items are available under the Emergency branch:

item name

access

description

Start Function Test

W

Used to trigger a function test for all emergency DALI lights.

Start Partial Duration Test

W

Used to trigger a partial duration test for all emergency DALI lights.

Start Duration Test

W

Used to trigger a duration test for all emergency DALI lights.

Start Battery Test

W

Used to trigger a battery test for all emergency DALI lights.

Test faulty devices only

RW

If set to True when a test is triggered, only DALI devices that failed the previous test will be submitted to the test.

Test Triggered

R

  • Changes from False to True after a test has beed triggered by writing to Start Function Test or Start Partial Duration Test.

  • Changes from True to False after the test result has been written to the database.

Use this data point as a callback to indicate that a test has been triggered.

Test Running

R

True, if an emergency DALI test is currently running.

Stop Test

W

Used to stop a running test.

Remaining Test Runtime

R

The remaining runtime in minutes of a triggered test.

Number Faulty Devices

R

The number of devices that failed on the latest test.

Faulty devices

R

Comma-separated list of device numbers of devices that did not pass the latest test.

Fault

R

True, if an emergency test of at least 1 DALI light failed.

Last test was

R

Shows the type of the last completed test, according to LaMPS test type encoding.

Last test faulted

R

True, if "Last test faulted" of at least 1 DALI light is currently true.

Last test stopped

R

True, if "Last test stopped" of at least 1 DALI light is currently true.

Converter defect

R

True, if "Converter defect" of at least 1 DALI light is currently true.

Battery fault or defect

R

True, if "Battery fault or defect" of at least 1 DALI light is currently true.

Fault emergency light

R

True, if "Fault emergency light" of at least 1 DALI light is currently true.

In addition, the following device-specific items are available under the sub tree "Emergency":

item name

description

Emergency Lights On/Off

True, if the gateway is in emergency mode.

Emergency Lighting Failure

True, if there is an emergency failure of at least one emergency DALI light.

Please note that these server items will only be created if emergency testing is available for the gateway. For these KNX/DALI gateways at least one DALI device must support emergency lighting tests. This means that there must be a "Emergency Mapping Definition" for at least one DALI device. Note that emergency testing is only available for self contained battery lamps.

For each configured DALI device, a sub tree with the name "Device<number>" is shown within the Server Item Tree. Each device has at least the following Server Items:

item name

description

Name

Human-readable name of the DALI device. The default name is "Device<number>". This name can be changed within the Device Name Mapping Definitions. 

Fault

True, if either a lamp or a device fault occurred.

Fault Lamp

True, if there is a lamp fault.

Fault Ballast

True, if there is a ballast fault.

Fault Converter

(Emergency lighting only) True, if there is a converter fault.

Test succeeded

True, if a response is received during the test.

If a device is also an emergency light (i.e. it has a valid emergency mapping definition), the following items are available in the sub tree "Emergency":

item name

description

Test Running

True, when an emergency DALI test is currently running.

Start Function Test

Used to trigger a function test for this device.

Start Duration Test

Used to trigger a duration test for this device.

Start Partial Duration Test

Used to trigger a partial duration test for this device.

Start Battery Test

Used to trigger a battery test for this device.

Stop Test

Used to stop a running test.

Remaining Test Runtime

Remaining runtime in minutes for a triggered test.

Last test was

Shows the type of the last test. 

valuedescription
0"No Test"
1"Function Test"
2"Partial duration test"
3"Duration test"
4"Battery test"
255"Test not supported"


Last test faulted

True, if there was no test result response. This may be the case when the DALI does not support emergency tests.

Converter defect

True, if the converter is defect.

Fault battery

True, if there is a battery fault.

Battery defect

True, if the battery is defect.

Fault emergency light

True, if there is an emergency light failure.

Max time function test exceeded

True, if the maximum time for the function test exceeded.

Max time duration test exceeded

True, if the maximum time for the duration test exceeded.

Function test failed

True, if the function test failed.

Duration test failed

True, if the duration test failed.

Test result

Test result: The raw data as received from the gateway. Time results have to be multiplied by 2 minutes; Battery charge status is from 0 to 255 and has to be converted to percentage.

Emergency testing server items per DALI device / results per test type

Following branches and server items are available for each DALI device, which is configured as emergency light:

  • FunctionTest branch: result of the latest function test.

item name

description

Last test faulted

True, if there was no test result response. This may be the case if the DALI device does not support emergency tests.

Function test failed

True, if the function test failed.

Fault Converter

True, if the device reported a converter fault.

Fault battery

True, if the device reported a battery fault.

Battery defect

True, if the device reported the battery as defect.

Battery fault or defect

True, if Fault battery or Battery defect is true.

Fault emergency light

True, if there is an emergency light failure.

Battery charging state

The battery charging state in percent.

  • PartialDurationTest branch: result of the latest partial duration test. (Not supported by Ipas, EAE gateways.)

item name

description

Last test faulted

True, if there was no test result response. This may be the case if the DALI device does not support emergency tests.

Duration test failed

True, if the duration test failed.

Fault Converter

True, if the device reported a converter fault.

Fault battery

True, if the device reported a battery fault.

Battery defect

True, if the device reported the battery as defect.

Battery fault or defect

True, if Fault battery or Battery defect is true.

Fault emergency light

True, if there is an emergency light failure.

Battery charging state

The battery charging state in percent.

  • DurationTest branch: results of the latest duration test.

item name

description

Last test faulted

True, if there was no test result response. This may be the case if the DALI device does not support emergency tests.

Duration test failed

True, if the duration test failed.

Fault Converter

True, if the device reported a converter fault.

Fault battery

True, if the device reported a battery fault.

Battery defect

True, if the device reported the battery as defect.

Battery fault or defect

True, if Fault battery or Battery defect is true.

Fault emergency light

True, if there is an emergency light failure.

Time period

Test duration in minutes.

  • BatteryTest branch: results of the latest battery test. (Not supported by EAE gateways.)

item name

description

Last test faulted

True, if there was no test result response. This may be the case if the DALI device does not support emergency tests.

Fault Converter

True, if the device reported a converter fault.

Fault battery

True, if the device reported a battery fault.

Battery defect

True, if the device reported the battery as defect.

Battery fault or defect

True, if Fault battery or Battery defect is true.

Fault emergency light

True, if there is an emergency light failure.

Battery charging state

The battery charging state in percent.

Device functions server items

If device functions (OnOff, Brightness, Operating Hours Counter) are configured in the Device name mapping definitions then the respective Server Items will be available in the Functions branch:

item name

description

On/Off

Switches the DALI light.

On/Off Status

Status of the DALI light (read-only).

Brightness

Sets the brightness of the DALI light.

Brightness Status

Brightness feedback of the DALI light (read-only).

OperatingHours

Current reading of the operating hours counter.

OperatingHoursReset

Resets the operating hours counter.

OperatingHoursAlarmThreshold

Sets the alarm threshold of the operating hours counter.

OperatingHoursAlarm

True, if the operating hours have exceeded the threshold.