Some gateways do not have a global KNX communication object for starting an emergency test and for getting the result – they have a separate object for each device. Therefore, the ItemIDs has to be configured for each emergency lighting separately.
This is done in the Emergency Test Mapping Defintions Table:
parameter | type | optional/mandatory | description | default |
---|
Name | string | M | Name of the Dali gateway that is used within the gateway definition. |
|
Path | string | O | Path of the Dali gateway that is used within the gateway definition. | not used |
Devices | device (case 1) or device range (case 2) | M | Case 1: A single DALI device is required for the following gateway types: Gira/Insta DALI Gateway Plus REG 218000 Hager Dali gateway KNX TYA670D Jung KNX DALI-Gateway Plus 2098 REGHE Ipas DaliControl MDT DaliControl IP Gateway Merten KNX DALI-Gateway Schneider KNX DALI-Gateway - Siemens KNX/DALI Gateway N 141/03, N 141/21, N 141/31
- Siemens KNX/DALI Gateway N 141/02
Case 2: A list of DALI devices or device ranges is allowed for all other gateway types that support emergency lighting, e.g. |
|
Start Test | ItemId | M for case 1 devices | Item that is used to start an emergency test. gateway types | description |
---|
Gira/Insta DALI Gateway Plus REG 218000 Hager Dali gateway KNX TYA670D Jung KNX DALI-Gateway Plus 2098 REGHE | KNX Object #433 + (device ID -1) * 17 (i.e. #433, #450, #467, ...) | Ipas DaliControl MDT DaliControl IP Gateway Merten KNX DALI-Gateway Schneider KNX DALI-Gateway | See here. | Siemens KNX/DALI Gateway N 141/03, N 141/21, N 141/31 | - Channel A:
- App version < 5: KNX Object #607 + (device ID -1) * 2 (i.e. #607, #609, ...)
- App version >= 5: KNX Object #690+ (device ID -1) * 2 (i.e. #690, #691, ...)
- Channel B:
- App version < 5: KNX Object #1306 + (device ID -1) * 2 (i.e. #1306, #1308, ...)
- App version >= 5: KNX Object #1472 + (device ID -1) * 2 (i.e. #1472, #1473, ...)
| Siemens KNX/DALI Gateway N 141/02 | KNX Object #146 + (device ID -1) * 8 (i.e. #146, #154, ...) |
|
|
Test Result | ItemId | M for case 1 devices | Item that provides the test result. Dependening on the gateway type, the following KNX communication objects have to be used: gateway types | description |
---|
Gira/Insta DALI Gateway Plus REG 218000 Hager Dali gateway KNX TYA670D Jung KNX DALI-Gateway Plus 2098 REGHE | KNX Object #432 + (device ID -1) * 17 (i.e. #432, #449, #466, ...) | Ipas DaliControl MDT DaliControl IP Gateway Merten KNX DALI-Gateway Schneider KNX DALI-Gateway | See here. | Siemens KNX/DALI Gateway N 141/03, N 141/21, N 141/31 | - Channel A:
- App version < 5: KNX Object #608 + (device ID -1) * 2 (i.e. #608, #610, ...)
- App version >= 5: KNX Object #691 + (device ID -1) * 2 (i.e. #691, #693, ...)
- Channel B:
- App version < 5: KNX Object #1307+ (device ID -1) * 2 (i.e. #1307, #1309, ...)
- App version >= 5: KNX Object #1473+ (device ID -1) * 2 (i.e. #1473, #1475, ...)
| Siemens KNX/DALI Gateway N 141/02 | KNX Object #147 + (device ID -1) * 8 (i.e. #147, #155, ...) |
|
|