Based on the configured UPS devices, a number of data points is available in the item tree. For each UPS device, a branch with its name is created within NETx\Module\LaMPS\UPS.
...
item name | access | description |
---|---|---|
Battery charging state | R | The battery charge state as used in reports. If BETA -- UPS definitions, col Battery level manual override is enabled and Battery charging state - manual is set, then the value of the latter data point is set here. Otherwise, Battery charging state - device is used. |
Battery charging state - device | R | The device reading of the battery. Value is taken from BETA -- UPS definitions, col Battery level. |
Battery charging state - manual | RW | Only present if BETA -- UPS definitions, col Battery level manual override is enabled. A value provided here will supersede Battery charging state - device in the final value in item Battery charging state. |
Battery charging state - manual reset | W | Only present if BETA -- UPS definitions, col Battery level manual override is enabled. Write 1 to this data point to relinquish a previously set value in Battery charging state - manual. |
Start Function Test | W | Write 1 to this data point to trigger a UPS function test. |
Start Partial Duration Test | W | Write 1 to this data point to trigger a UPS partial duration test. |
Test faulty devices only | RW | If set to True when a test is triggered, only DALI devices that failed the previous test will be submitted to the test. |
Test Locked | RW | If set to True when a test is triggered, the test will abort immediately and a non-successful test is recorded in the database. |
Test Triggered | R |
Use this data point as a callback to indicate that a test has been triggered. |
Test Running | R |
Use this data point as a callback to indicate that a test is currently running. |
Stop Test | W | Write 1 to this data point to stop a running UPS test. |
Remaining Test Runtime | R | The remaining runtime in minutes of a triggered test. |
Number Faulty Devices | R | The number of devices that failed on the latest test. |
Last triggered test | R | Shows the type of the last triggered test: 0: no test 1: function test 2: partial duration test 3: duration test 4: battery test , according to LaMPS test type encoding. |
Last test was | R | Shows the type of the last completed test. Encoding as in Last triggered test. |
Last test stopped | R | True if the last test was stopped through the Stop Test data point. |