If you run the BMS Server behind a firewall you might need to open specific ports so that the server can be reached from the outside. This article explains differerent communication paths of each application protocol.

application protocolIP protocoldefault portdirectionconfiguration
BACnetUDP47808inbound, outboundBMS Studio / BACnet / Driver Configuration / BACnet.Port
Fidelio/Opera 5003inboundBMS Studio / Modules / Fidelio/Opera Interface / Driver Configuration / FIDELIO.Port
KabaTCP6005inboundBMS Studio / Modules / Kaba / Driver Configuration / xio.Kaba.LocalPort
KNXUDP3671inbound, outboundBMS Studio / KNX / KNX Gateway Defintions / Port
ModbusTCP, UDP502inbound, outboundBMS Studio / Modbus / Modbus Device Definitions / Device Type
OPC DATCP, UDP135inbound, ???see this article for full DCOM configuration details
OPC UA    
SNMPUDP161inboundBMS Studio / SNMP / SNMP Device Definitions / Port
VingCardTCP4000inboundBMS Studio / Modules / VingCard / Driver Configuration / xio.VingCard.LocalPort
VNETTCP4530inboundBMS Studio / Server Configuration / VNET.NetworkPortNumber
WebServerTCP80inboundBMS Studio / Server Configuration / VNET.WebServerPort