If you run the BMS Server behind a firewall you might need to open specific ports so that the server can be reached from the outside. This article explains differerent communication paths of each application.

applicationIP protocoldefault portconfiguration
BACnetUDP47808BMS Studio / BACnet / Driver Configuration / BACnet.Port
Fidelio/Opera 5003BMS Studio / Modules / Fidelio/Opera Interface / Driver Configuration / FIDELIO.Port
KabaTCP6005BMS Studio / Modules / Kaba / Driver Configuration / xio.Kaba.LocalPort
KNXUDP3671BMS Studio / KNX / KNX Gateway Defintions / Port
ModbusTCP, UDP502BMS Studio / Modbus / Modbus Device Definitions / Device Type
OPC DATCP, UDP135see this article for full DCOM configuration details
OPC UA   
SNMPUDP161BMS Studio / SNMP / SNMP Device Definitions / Port
VingCardTCP4000BMS Studio / Modules / VingCard / Driver Configuration / xio.VingCard.LocalPort
VNETTCP4530BMS Studio / Server Configuration / VNET.NetworkPortNumber
WebServerTCP80BMS Studio / Server Configuration / VNET.WebServerPort