If you run the BMS Server behind a firewall you might need to open specific ports so that the server can be reached from the outside. This article explains differerent communication paths of each application.
application | IP protocol | default port | configuration |
---|---|---|---|
BACnet | UDP | 47808 | BMS Studio / BACnet / Driver Configuration / BACnet.Port |
Fidelio/Opera | 5003 | BMS Studio / Modules / Fidelio/Opera Interface / Driver Configuration / FIDELIO.Port | |
Kaba | TCP | 6005 | BMS Studio / Modules / Kaba / Driver Configuration / xio.Kaba.LocalPort |
KNX | UDP | 3671 | BMS Studio / KNX / KNX Gateway Defintions / Port |
Modbus | TCP, UDP | 502 | BMS Studio / Modbus / Modbus Device Definitions / Device Type |
OPC DA | TCP, UDP | 135 | see this article for full DCOM configuration details |
OPC UA | |||
SNMP | UDP | 161 | BMS Studio / SNMP / SNMP Device Definitions / Port |
VingCard | TCP | 4000 | BMS Studio / Modules / VingCard / Driver Configuration / xio.VingCard.LocalPort |
VNET | TCP | 4530 | BMS Studio / Server Configuration / VNET.NetworkPortNumber |
WebServer | TCP | 80 | BMS Studio / Server Configuration / VNET.WebServerPort |