Firewall settings of the BMS Server
Firewall settings of the BMS Server
If you run the BMS Server behind a firewall you might need to open specific ports so that the server can be reached from the outside. This article explains differerent communication paths of each application protocol.
Accessing BMS Server through NETx Clients
Application protocol | IP protocol | Default port | Direction | Configuration |
---|---|---|---|---|
VNET | TCP | 4530 | inbound | BMS Studio / Server / Server Configuration / VNET.NetworkPortNumber |
WebServer | TCP | 80 | inbound | BMS Studio / Server / Server Configuration / VNET.WebServerPort |
Main/Backup | UDP | 20556 | inbound, outbound | BMS Studio / Server / N-Mesh Configuration / NMESH.NetworkPortNumber |
Accessing BMS Server through 3rd party management clients
Application protocol | IP protocol | Default port | Direction | Configuration |
---|---|---|---|---|
OPC DA | TCP, UDP | 135 | inbound, outbound | See this article for full DCOM configuration details |
OPC UA | TCP | 48400, 48401 | inbound | BMS Studio / Modules / OPCUA / OPC UA configuration / xio.OPCUA.LocalTCPPort + xio.OPCUA.LocalHTTPPort |
BACnet | UDP | 47808 | inbound, outbound | BMS Studio / BACnet / Driver Configuration / BACnet.Port |
oBIX | TCP | 9000 | inbound | BMS Studio / Modules / oBIX / Driver configuration / xio.oBIX.LocalPort |
Access to field level devices
Application protocol | IP protocol | Default port | direction | Configuration |
---|---|---|---|---|
KNX | UDP | 3671 | inbound, outbound | BMS Studio / KNX / KNX Gateway Defintions / Port |
BACnet | UDP | 47808 | inbound, outbound | BMS Studio / BACnet / Driver Configuration / BACnet.Port |
Modbus TCP | TCP | 502 | inbound, outbound | BMS Studio / Modbus / Modbus Device Definitions / Port |
Modbus RTU | TCP, UDP | No default | inbound, outbound | BMS Studio / Modbus / Modbus Device Definitions / Port |
SNMP Polling | UDP | 161 | inbound, outbound | BMS Studio / SNMP / SNMP Device Definitions / Port |
SNMP Traps | UDP | 162 | inbound | BMS Studio / SNMP / Traps / Listener definitions / Port |
Fidelio/Opera | TCP | 5003 | inbound | BMS Studio / Modules / Fidelio/Opera Interface / Driver Configuration / FIDELIO.Port |
Kaba | TCP | 6005 | inbound | BMS Studio / Modules / Kaba / Driver Configuration / xio.Kaba.LocalPort |
VingCard | TCP | 4000 | inbound | BMS Studio / Modules / VingCard / Driver Configuration / xio.VingCard.LocalPort |
Related articles appear here based on the labels you select. Click to edit the macro and add or change labels.Related articles
, multiple selections available,
Related content
Firewall settings for the BMS Platform
Firewall settings for the BMS Platform
More like this
NETx BMS Platform and NETx Multi Protocol Server Documentation
NETx BMS Platform and NETx Multi Protocol Server Documentation
More like this
General server configuration
General server configuration
More like this
Tutorial: Integrate BACnet devices and their objects
Tutorial: Integrate BACnet devices and their objects
More like this
Client Configuration
Client Configuration
More like this
The way how the NETx Server service works
The way how the NETx Server service works
More like this