If you run the BMS Server behind a firewall you might need to open specific ports so that the server can be reached from the outside. This article explains differerent communication paths of each application protocol.
...
Application protocol | IP protocol | Default port | direction | Configuration |
---|---|---|---|---|
KNX | UDP | 3671 | inbound, outbound | BMS Studio / KNX / KNX Gateway Defintions / Port |
BACnet | UDP | 47808 | inbound, outbound | BMS Studio / BACnet / Driver Configuration / BACnet.Port |
Modbus TCP | TCP, UDP | 502 | inbound, outbound | BMS Studio / Modbus / Modbus Device Definitions / Port |
Modbus RTU | TCP, UDP | No default | inbound, outbound | BMS Studio / Modbus / Modbus Device Definitions / Port |
SNMP Polling | UDP | 161 | inbound, outbound | BMS Studio / SNMP / SNMP Device Definitions / Port |
SNMP Traps | UDP | 162 | inbound | BMS Studio / SNMP / Traps / Listener definitions / Port |
Fidelio/Opera | TCP | 5003 | inbound | BMS Studio / Modules / Fidelio/Opera Interface / Driver Configuration / FIDELIO.Port |
Kaba | TCP | 6005 | inbound | BMS Studio / Modules / Kaba / Driver Configuration / xio.Kaba.LocalPort |
VingCard | TCP | 4000 | inbound | BMS Studio / Modules / VingCard / Driver Configuration / xio.VingCard.LocalPort |