Firewall settings of the BMS Server
Firewall settings of the BMS Server
If you run the BMS Server behind a firewall you might need to open specific ports so that the server can be reached from the outside. This article explains differerent communication paths of each application protocol.
Accessing BMS Server through NETx Clients
Application protocol | IP protocol | Default port | Direction | Configuration |
---|---|---|---|---|
VNET | TCP | 4530 | inbound | BMS Studio / Server / Server Configuration / VNET.NetworkPortNumber |
WebServer | TCP | 80 | inbound | BMS Studio / Server / Server Configuration / VNET.WebServerPort |
Main/Backup | UDP | 20556 | inbound, outbound | BMS Studio / Server / N-Mesh Configuration / NMESH.NetworkPortNumber |
Accessing BMS Server through 3rd party management clients
Application protocol | IP protocol | Default port | Direction | Configuration |
---|---|---|---|---|
OPC DA | TCP, UDP | 135 | inbound, outbound | See this article for full DCOM configuration details |
OPC UA | TCP | 48400, 48401 | inbound | BMS Studio / Modules / OPCUA / OPC UA configuration / xio.OPCUA.LocalTCPPort + xio.OPCUA.LocalHTTPPort |
BACnet | UDP | 47808 | inbound, outbound | BMS Studio / BACnet / Driver Configuration / BACnet.Port |
oBIX | TCP | 9000 | inbound | BMS Studio / Modules / oBIX / Driver configuration / xio.oBIX.LocalPort |
Access to field level devices
Application protocol | IP protocol | Default port | direction | Configuration |
---|---|---|---|---|
KNX | UDP | 3671 | inbound, outbound | BMS Studio / KNX / KNX Gateway Defintions / Port |
BACnet | UDP | 47808 | inbound, outbound | BMS Studio / BACnet / Driver Configuration / BACnet.Port |
Modbus TCP | TCP | 502 | inbound, outbound | BMS Studio / Modbus / Modbus Device Definitions / Port |
Modbus RTU | TCP, UDP | No default | inbound, outbound | BMS Studio / Modbus / Modbus Device Definitions / Port |
SNMP Polling | UDP | 161 | inbound, outbound | BMS Studio / SNMP / SNMP Device Definitions / Port |
SNMP Traps | UDP | 162 | inbound | BMS Studio / SNMP / Traps / Listener definitions / Port |
Fidelio/Opera | TCP | 5003 | inbound | BMS Studio / Modules / Fidelio/Opera Interface / Driver Configuration / FIDELIO.Port |
Kaba | TCP | 6005 | inbound | BMS Studio / Modules / Kaba / Driver Configuration / xio.Kaba.LocalPort |
VingCard | TCP | 4000 | inbound | BMS Studio / Modules / VingCard / Driver Configuration / xio.VingCard.LocalPort |
Related articles appear here based on the labels you select. Click to edit the macro and add or change labels.Related articles
, multiple selections available,
Related content
Webvisu1: Creating a web visualization for KNX
Webvisu1: Creating a web visualization for KNX
Read with this
Firewall settings for the BMS Platform
Firewall settings for the BMS Platform
More like this
Accessing the BMS Server in a local network from the internet
Accessing the BMS Server in a local network from the internet
More like this
Accessing the NETx BMS Web Manager in a local network from the internet
Accessing the NETx BMS Web Manager in a local network from the internet
More like this
Connection of BMS visualization clients
Connection of BMS visualization clients
More like this
Service Control application
Service Control application
More like this