If you run the BMS Server behind a firewall you might need to open specific ports so that the server can be reached from the outside. This article explains differerent communication paths of each application protocol.
...
Accessing BMS Server through NETx Clients
Application protocol | IP protocol | default port | direction | configuration | BACnet | UDP | 47808Default port | Direction | Configuration |
---|---|---|---|---|---|---|---|---|---|
VNET | TCP | 4530 | inbound | BMS Studio / Server / Server Configuration / VNET.NetworkPortNumber | |||||
WebServer | TCP | 80 | inbound | BMS Studio / Server / Server Configuration / VNET.WebServerPort | |||||
Main/Backup | UDP | 20556 | inbound, outbound | BMS Studio / | BACnetServer / | DriverN-Mesh Configuration / | BACnet.PortFidelio/Opera | 5003NMESH.NetworkPortNumber |
Accessing BMS Server through 3rd party management clients
Application protocol | IP protocol | Default port | Direction | Configuration |
---|---|---|---|---|
OPC DA | TCP, UDP | 135 | inbound, outbound | See this article for full DCOM configuration details |
OPC UA | TCP | 48400, 48401 | inbound | BMS Studio / Modules / Fidelio/Opera Interface OPCUA / OPC UA configuration / xio.OPCUA.LocalTCPPort + xio.OPCUA.LocalHTTPPort |
BACnet | UDP | 47808 | inbound, outbound | BMS Studio / BACnet / Driver Configuration / FIDELIOBACnet.Port |
KabaoBIX | TCP | 60059000 | inbound | BMS Studio / Modules / Kaba oBIX / Driver Configuration configuration / xio.KabaoBIX.LocalPort |
Access to field level devices
Application protocol | IP protocol | Default port | direction | Configuration | |||
---|---|---|---|---|---|---|---|
KNX | UDP | 3671 | inbound, outbound | BMS Studio / KNX / KNX Gateway Defintions / Port | |||
BACnet | UDP | 47808 | inbound, outbound | BMS Studio / BACnet / Driver Configuration / BACnet.Port | |||
Modbus TCP | TCP | , UDP502 | inbound, outbound | BMS Studio / Modbus / Modbus Device Definitions / Device TypeOPC DAPort | |||
Modbus RTU | TCP, UDP | 135No default | inbound, | ???see this article for full DCOM configuration details | |||
OPC UA | |||||||
SNMP | UDP | 161outbound | BMS Studio / Modbus / Modbus Device Definitions / Port | ||||
SNMP Polling | UDP | 161 | inbound, outbound | BMS Studio / SNMP / SNMP Device Definitions / Port | |||
SNMP Traps | UDP | 162 | inbound | BMS Studio / SNMP / SNMP Device DefinitionsTraps / Listener definitions / Port | VingCard|||
Fidelio/Opera | TCP4000 | 5003 | inbound | BMS Studio / Modules / Fidelio/ | VingCardOpera Interface / Driver Configuration / | xioFIDELIO. | VingCard.LocalPortPortVNET |
Kaba | TCP | 45306005 | inbound | BMS Studio / Modules / Kaba / | ServerDriver Configuration / | VNETxio.Kaba. | NetworkPortNumberLocalPort |
VingCard | TCP | 804000 | inbound | BMS Studio / | ServerModules / VingCard / Driver Configuration / | VNETxio.VingCard. | WebServerPortLocalPort |