If you run the BMS Server behind a firewall you might need to open specific ports so that the server can be reached from the outside. This article explains differerent communication paths of each application protocol.

...

Accessing BMS Server through NETx Clients

47808 BACnet Driver BACnet.Port
Application protocolIP protocoldefault portconfigurationBACnetUDPDefault portDirectionConfiguration
VNETTCP4530inboundBMS Studio / Server / Server Configuration / VNET.NetworkPortNumber
WebServerTCP80inboundBMS Studio / Server / Server Configuration / VNET.WebServerPort
Main/BackupUDP20556inbound, outboundBMS Studio / Server / N-Mesh Configuration / Fidelio/Opera 5003NMESH.NetworkPortNumber

Accessing BMS Server through 3rd party management clients

Application protocolIP protocolDefault portDirectionConfiguration
OPC DATCP, UDP135inbound, outboundSee this article for full DCOM configuration details
OPC UATCP48400, 48401inboundBMS Studio / Modules / Fidelio/Opera Interface / OPCUA / OPC UA configuration / xio.OPCUA.LocalTCPPort + xio.OPCUA.LocalHTTPPort
BACnetUDP47808inbound, outboundBMS Studio / BACnet / Driver Configuration / FIDELIOBACnet.Port
KabaoBIXTCP90006005inboundBMS Studio / Modules / Kaba oBIX / Driver Configuration configuration / xio.KabaoBIX.LocalPort

Access to field level devices

, UDPVingCard VingCard xioVingCard.LocalPort4530 Server VNETNetworkPortNumberWebServer80 Server VNETWebServerPort
Application protocolIP protocolDefault portdirectionConfiguration
KNXUDP3671inbound, outboundBMS Studio / KNX / KNX Gateway Defintions / Port
BACnetUDP47808inbound, outboundBMS Studio / BACnet / Driver Configuration / BACnet.Port
Modbus TCPTCP502inbound, outboundBMS Studio / Modbus / Modbus Device Definitions / Device TypeOPC DAPort
Modbus RTUTCP, UDP135see this article for full DCOM configuration details
OPC UA   
SNMPNo defaultinbound, outboundBMS Studio / Modbus / Modbus Device Definitions / Port
SNMP PollingUDP161inbound, outbound

BMS Studio / SNMP / SNMP Device Definitions / Port

SNMP TrapsUDP162inbound

BMS Studio / SNMP / Traps / Listener definitions / Port

Fidelio/OperaTCP40005003inboundBMS Studio / Modules / Fidelio/Opera Interface / Driver Configuration / FIDELIO.PortVNET
KabaTCP6005inboundBMS Studio / Modules / Kaba / Driver Configuration / xio.Kaba.LocalPort
VingCardTCP4000inboundBMS Studio / Modules / VingCard / Driver Configuration / xio.VingCard.LocalPort


Related articles appear here based on the labels you select. Click to edit the macro and add or change labels.Related articles

Filter by label (Content by label)
showLabelsfalse
max5
spacesBMS20
showSpacefalse
sortmodified
reversetrue
typepage
cqllabel in ("bms-server","firewall","network") and type = "page" and space = "BMS20"
labelsnetwork firewall bms-server

...