NETx LaMPS Module

Functionality

The NETx LaMPS Module is an extension to the NETx BMS Server that has the aim to make the management of lighting control systems more easier. It consists of two parts: the first one provides general functionality for monitoring lighting circuits. It is possible to monitor the operating hours, and defining thresholds for triggering alarms. In addition it is possible to provide an approximation of energy and power calculation if no smart meter is available. 

The second part is dedicated to the management of DALI gateways and their devices. The Digital Addressable Lighting Interface (DALI) protocol is an application specific technology that is dedicated to lighting systems. Since it is a pure field level protocol without enhanced management features, it is integrated into other building automation technologies. The most important and most commonly used system for this integration purpose is KNX. So called KNX/DALI gateways are providing interfaces between the DALI devices and the KNX network. In addition to simply forwarding commands (e.g. on/off, dimming commands, ...) and information (e.g. on/off status, current brightness value), these KNX/DALI gateways provide sophisticated and enhanced functions. One of the most important feature is the testing of the functionality of the DALI devices.

However, the implementation of this function testing within the KNX/DALI gateways highly depends on the manufacturer of the gateway. Each vendor has its own way how function testing services are provided and how the test results are represented. This also concerns the mapping of this information to KNX communication objects. Even worse, most of the time a simple read and write to these KNX communication objects is not sufficient since a dedicated command sequence is necessary. A typical example is the reading of the fault status of a DALI device. First, the device has to be selected by sending the DALI number to a dedicated KNX group address and afterwards the fault status objects have to be read. This results in a complexity which is a major problem for system integrators and electrical engineers who have the task to provide such functionality.

To make the management of KNX/DALI gateways more easier, the NETx BMS Server is providing a dedicate module called LaMPS. The main goal of LaMPS is to provide a generic interface to initiate DALI tests independent of the used KNX/DALI gateway vendor. One of the most important functionality of KNX/DALI gateways is the possibility to monitor the fault state of DALI gateways and their DALI devices. This includes triggering of DALI device tests, the evaluation of test results and the monitoring of the fault states. Since each KNX/DALI gateway vendor are using their own KNX communication objects to provide this functionality, LaMPS provides an abstraction of these vendor-specific implementations. 

Currently, the following KNX/DALI gateways are supported:

  • ABB DG/S 1.1, DG/S x.64.1.1, DGN/S 1.16.1

  • B.E.G. DALI/KNX-Gateway
  • EAE DA100, DA101
  • Eelectron KNX/DALI Gateway (Tunable White)
  • Gira/Insta DALI Gateway Plus REG 218000

  • Hager Dali gateway KNX TYA670D

  • Ipas DaliControl e64
  • Jung KNX DALI-Gateway Plus 2098/2099 REGHE

  • MDT DaliControl IP Gateway SCN-DALI64.02

  • Merten KNX DALI-Gateway REG-K/1/16(64)/64/IP1 (MEG6725-0001)

  • Schneider KNX DALI-Gateway MTN6725-0001

  • Siemens KNX/DALI Gateway N 141/03, N 141/21, N 141/31

  • Siemens KNX/DALI Gateway N 141/02

  • Zennio DALIBOX Interface 64-32


If you are using KNX/DALI gateways that are not yet supported, please contact us. Other DALI gateways from other manufacturers can be included on request.

Installation

LaMPS is provided for the NETx BMS Server as extension module. This means that it is not included within the setup per default. 

To install LaMPS, open the BMS Studio and shutdown the BMS Server. Afterwards, start the Extension Manager via the menu ("Extensions" --> "Manager" --> "Start Extension Manager ...").

Within the dialog, select "LaMPS" and press the "install" button. After having installed the LaMPS module, close the BMS studio and reopen it. Within the "Modules" menu of the BMS Studio you will find a new sub menu "LaMPS". It contains entries for all definitions that are necessary for configuration the LaMPS module.

Licensing

The LaMPS functionality is not included in a standard license for the NETx BMS Server. This means that an extra license has to be bought if the LaMPS module is required in your project. 

The price that has to be paid in addition to the normal fees of the BMS Server license of this extra fee is a fix amount which is independent of used amount of DALI gateways and DALI devices. In addition to this fix amount, 1 data point is counted for each DALI device that is used within the LaMPS module. These data points are subtracted from the total amount of available data points of your BMS Server license. For more information about the cost please contact our sales team.

The extra license itself is an option to the standard BMS Server licenses. This means the licensing process is exactly the same as for a normal BMS Server license. For a softlock license, the LaMPS option is encoded within your License ID and Unlock Code. For hardlock, the option is stored on your USB license dongle. 

In order to test LaMPS, LaMPS is included within the demo license of the NETx BMS Server. This means that you can test the LaMPS module for 90 days for free.

Configuration

To be able to provide the required functionality, a correct ETS configuration of the KNX/DALI gateways is of utmost importance. Each KNX/DALI gateway has a multitude of different KNX communication objects and parameter. Only if the correct parameters are set within the ETS and only if the required KNX communication objects are correctly assigned to KNX group addresses, a proper functionality of LaMPS can be guaranteed.

To make the configuration and most important the transfer of the configuration from ETS to the NETx BMS Server more easier, an extended ETS app called NETx BMS App Secure has been developed. The NETx BMS App Secure includes the possibility to export the required KNX/DALI gateway configuration automatically. In addition, it warns the user if required or suggested ETS parameters are not set accordingly. 

If the LaMPS option is set within the NETx BMS App Secure, all required configuration data is included within the ".nxe" export file. For each KNX/DALI gateway type, one BMS definition file exist. All these definition files are accessible within the BMS studio via the menu "Modules" --> "LaMPS" --> "DALI".

In the remainder of this section, the different definition files are explained in detail. 

Module configuration

Here common configuration settings for the NETx LaMPS Module can be changed:

  • Function test timeout (s): timeout for DALI emergency function tests. If no test result is  received after this timeout is expired, the test fails. Default is 30 seconds.
  • Duration test timeout (s): timeout for DALI emergency duration tests. If no test result is  received after this timeout is expired, the test fails. Default is 10800 seconds (3 hours).
  • Partial during test timeout (s): timeout for DALI emergency partial duration tests. If no test result is  received after this timeout is expired, the test fails. Default is 10800 seconds (3 hours).
  • Battery test timeout (s): timeout for DALI emergency battery tests. If no test result is  received after this timeout is expired, the test fails. Default is 10800 seconds (3 hours).

Circuit definitions

Here common lighting circuits can be defined that shall be monitored by the NETx LaMPS Module.  

  • Name (string): name of circuit 
  • Path (string, optional, default: not used): path used for structure within NETx BMS Server
  • OnOff ItemId (ItemID): ItemID that is used to turn on and off the circuit. If a separate status item is not used, this item also provides the status for calculating the operating hours
  • OnOff Status ItemId (ItemID, optional, default: not used): ItemID that provides the on/off status for this circuit. This status is also used for calculating the operating hours. If not used, the OnOff ItemID is used instead.
  • Operating Time Warning Threshold (number, optional, default: not used): warning threshold for operating hours. If exceeded, the warning alarm item will turn to true. The current threshold can also be changed during runtime via the corresponding item.
  • Operating Time Alarm Threshold (number, optional, default: not used): alarm threshold for operating hours. If exceeded, the alarm alarm item will turn to true. The current threshold can also be changed during runtime via the corresponding item.
  • Brightness ItemId (ItemID, optional, default: not used): ItemID that can be used to change the brightness of a dimmable light. 
  • Brightness Status ItemId (ItemID, optional, default: not used): ItemID that provides the current brightness value of a dimmable light.
  • Brightness Scale Factor (number, optional, default: 1): scale factor for the brightness value
  • Current ItemId (ItemID, optional, default: not used): if available the used current can be provided by this item.
  • Current Scale Factor (number, optional, default: 1): scale factor for the current. 
  • Current Lower Warning Threshold (number, optional, default: not used): here a lower warning threshold for monitoring the current can be specified. The current threshold can also be changed during runtime via the corresponding item.
  • Current Lower Alarm Threshold (number, optional, default: not used): here a lower alarm threshold for monitoring the current can be specified. The current threshold can also be changed during runtime via the corresponding item.
  • Current Higher Alarm Threshold (number, optional, default: not used): here a higher warning threshold for monitoring the current can be specified. The current threshold can also be changed during runtime via the corresponding item.
  • Current Higher Warning Threshold (number, optional, default: not used): here a higher alarm threshold for monitoring the current can be specified. The current threshold can also be changed during runtime via the corresponding item.
  • Voltage ItemId (ItemID, optional, default: not used): if availale the current voltage can be provided by this item.
  • Voltage Scale Factor (number, optional, default: 1): scale factor for the voltage.
  • Voltage Lower Warning Threshold (number, optional, default: not used): here a lower warning threshold for monitoring the voltage can be specified. The current threshold can also be changed during runtime via the corresponding item.
  • Voltage Lower Alarm Threshold (number, optional, default: not used): here a lower alarm threshold for monitoring the voltage can be specified. The current threshold can also be changed during runtime via the corresponding item.
  • Voltage Higher Warning Threshold (number, optional, default: not used): here a higher warning threshold for monitoring the voltage can be specified. The current threshold can also be changed during runtime via the corresponding item.
  • Voltage Higher Alarm Threshold (number, optional, default: not used): here a higher alarm threshold for monitoring the voltage can be specified. The current threshold can also be changed during runtime via the corresponding item.
  • Power ItemId (ItemID, optional, default: not used): if availabe the current power value can be provided by this item.
  • Power Scale Factor (number, optional, default: 1): scale factor for the power value.
  • Power Approximate (bool, optional, default: False): if enabled, an estimated power value based on the current and voltage is calculated. Note that this is calculation is only a rough estimation since the accuracy depends sending or polling interval of the current and voltage values.
  • Energy ItemId (ItemID, optional, default: not used): if availabe the current energy value can be provided by this item.
  • Energy Scale Factor (number, optional, default: 1): scale factor for the energy value.
  • Energy Approximate (bool, optional, default: False): if enabled, an estimated energy value based on the current and voltage is calculated. Note that this is calculation is only a rough estimation since the accuracy depends sending or polling interval of the current and voltage values.
  • Persistent (bool, optional, default: False): if set to true, all items are set to persistent i.e. the last values are restored after server startup.
  • Historical (bool, optional, default: False): if set to true, all values are stored within the historical database.
  • Redundant (bool, optional, default: True): if set to true, all items are synchronized with the backup server if available.

KNX/DALI common configuration options

Some configuration options are common to all KNX/DALI gateways. These are the following:

  • Name (string): name of DALI gateway that identifies the gateway within the NETx BMS Server. The name must be unique for all DALI gateways since it is part of the item ID.
  • Path (string, optional): path used for structure within NETx BMS Server 
  • Devices (device range, optional): list of DALI devices that are connected to this DALI gateway. The list is a comma separated list of DALI device numbers (starting with 1). In addition, specifying a device range is also possible. If no devices are specified, only the general device-independent functionality (e.g. DALI power fault) is available. Some examples of valid device lists:
    • 1
    • 1,2,5,6
    • 1-10,12,15-22
  • «gateway specific configuration options»

  • Poll Device (bool, default: True): specifies whether dedicated communication objects shall be polled or not. All communication objects that are affected by this polling are marked as "polled" within this documentation. If this parameter is set to false, the gateway must be configured in a way that the gateway automatically pushes the data to the KNX bus when it changes ("send on change"). 
  • Poll Interval (number, default: 5): polling interval in seconds.
  • Device Timeout (number, default: 1): timeout in seconds that LaMPS expects an answer to a read request.
  • Trigger Test on Connect (bool, default: False): if true, a DALI test is triggered when the KNXnet/IP tunneling connection is available
  • Trigger Test on Faults (bool, default: False): if true, a DALI test is triggered when a fault occurs

ABB DG/S 1.1

The ABB DG/S 1.1 support two different DALI channels – channel A and channel B. For each channel, one definition has to be added within the ABB DG/S 1.1 definition table. If you are using both channels of a single gateway, you have to distinguish them only be the name. For example, you can use "My DALI Gateway - Channel A" and "My DALI Gateway - Channel B" as names for the two definitions.

For each channel, the following configuration options are available:

  • «common configuration options»
  • Fault Dali (ItemId, KNX Object #4 or #22, polled, mandatory)
  • Fault Lamps (ItemId, KNX Object #5 or #23, polled, mandatory)
  • Fault Device (ItemId, KNX Object #6 or #24, polled, mandatory)
  • Select Device (ItemId, KNX Object #7 or #25, mandatory)
  • Selected Device OnOff (ItemId, KNX Object #8 or #26, optional)
  • Selected Device Lamp Failure (ItemId, KNX Object #15 or #33, mandatory)
  • Selected Device Device Failure (ItemId, KNX Object #16 or #34, mandatory)
  • «common configuration options»
  • Change of device sends faults (bool, default: False): if true, the gateway automatically sends fault information when a new device is selected

  • Change of device sends status (bool, default: False): if true,  the gateway automatically sends status information when a new device is selected

ABB DG/S x.64.1.1

For each gateway the following configuration options are available:

  • «common configuration options»
  • Fault Lamps (ItemId, KNX Object #19 or #1133, polled, mandatory): this communication object is true if there is a lamp error for at least 1 DALI device.
  • Fault Ballast (ItemId, KNX Object #20 or #1134, polled, mandatory): this communication object is true if there is a ballast error for at least 1 DALI device.
  • Fault DALI (ItemId, KNX Object #18 or #1132, polled, optional): this communication object is true if there is a general DALI error.
  • Fault addressed (ItemId, KNX Object #21 or #1135, mandatory): this communication object is used to trigger a normal DALI request and to get the test result.
  • Emergency Test Start (ItemId, KNX Object #40 or #1154, optional):  this communication object is used to trigger an emergency DALI test for a dedicated device.
  • Emergency Test Result (ItemId, KNX Object #42 or #1156, optional): this communication object is used to get the result of an emergency DALI test.
  • EmergencyTestTimeout (int, default 10s): specifies how long the driver will wait between sending two emergency start requests.
  • «common configuration options»
 The group object "Emergency Test Start" (#40 or #1154) has to be configured for "Yes, DGN/S1.16.1 format" within ETS. Otherwise the emergency lighting tests will not work.

The ABB DG/S x.64.1.1 gateway uses emergency test start and result objects for all devices on one channel – there are no individual objects for each emergency ballast as it is for other gateways. Therefore, there will appear no entry within the Emergency Mapping Definitions. If the emergency configuration is enabled it will appear within the ABB DG/S x.64.1.1 gateway definition.

ABB DGN/S 1.16.1

For each gateway the following configuration options are available:

  • «common configuration options»
  • Fault Lamps (ItemId, KNX Object #17, polled, mandatory): this communication object is true if there is a lamp error for at least 1 DALI device.
  • Fault Ballast (ItemId, KNX Object #18, polled, mandatory): this communication object is true if there is a ballast error for at least 1 DALI device.
  • Fault DALI (ItemId, KNX Object #19, polled, optional): this communication object is true if there is a general DALI error.
  • Diagnostics (ItemId, KNX Object #25, mandatory): this communication object is used to trigger a normal DALI request and to get the test result.
  • Emergency Test Start (ItemId, KNX Object #31, optional):  this communication object is used to trigger an emergency DALI test for a dedicated device.
  • Emergency Test Result (ItemId, KNX Object #33, optional): this communication object is used to get the result of an emergency DALI test.
  • Emergency Mode Active (ItemId, KNX Object #35, optional): if true, the DALI emergency lighting mode is active.
  • EmergencyTestTimeout (int, default 10s): specifies how long the driver will wait between sending two emergency start requests.
  • «common configuration options»

The ABB DGN/S 1.16.1 gateway uses emergency test start and result objects for all devices on one channel – there are no individual objects for each emergency ballast as it is for other gateways. Therefore, there will appear no entry within the Emergency Mapping Definitions. If the emergency configuration is enabled it will appear within the ABB DGN/S 1.16.1 gateway definition.

EAE DA 100

For each gateway the following configuration options are available:

  • «common configuration options»
  • Fault Lamp (ItemId, KNX Object #12, polled, mandatory): this communication object is true if there is a lamp error for at least 1 DALI device.
  • Fault Ballast (ItemId, KNX Object #13, polled, mandatory): this communication object is true if there is a ballast error for at least 1 DALI device.
  • Fault Converter (ItemId, KNX Object #14, polled, optional): this communication object is true if there is a converter error for at least 1 DALI device.
  • Fault gateway supply (ItemId, KNX Object #11,optional): this communication object is true if there is a general gateway supply error.
  • Fault mains connected supply (ItemId, KNX Object #16,optional): this communication object is true if there is a mains connected supply error.
  • Device Status (ItemId, KNX Object #3, mandatory): this communication object is used to trigger a normal DALI request and to get the test result.
  • Emergency Test Start (ItemId, KNX Object #4, optional):  this communication object is used to trigger an emergency DALI test.
  • EmergencyTestTimeout (int, default 10s): specifies how long the driver will wait between sending two emergency start requests.
  • «common configuration options»

EAE DA 101

For each gateway the following configuration options are available:

  • «common configuration options»
  • Fault Lamp (ItemId, KNX Object #14, polled, mandatory): this communication object is true if there is a lamp error for at least 1 DALI device.
  • Fault Ballast (ItemId, KNX Object #15, polled, mandatory): this communication object is true if there is a ballast error for at least 1 DALI device.
  • Fault Converter (ItemId, KNX Object #16, polled, optional): this communication object is true if there is a converter error for at least 1 DALI device.
  • Fault DALI (ItemId, KNX Object #12,optional): this communication object is true if there is a general DALI error.
  • Fault mains connected supply (ItemId, KNX Object #13,optional): this communication object is true if there is a mains connected supply error.
  • Device Status (ItemId, KNX Object #7, mandatory): this communication object is used to trigger a normal DALI request and to get the test result.
  • Emergency Test Start (ItemId, KNX Object #2, optional):  this communication object is used to trigger an emergency DALI test.
  • EmergencyTestTimeout (int, default 10s): specifies how long the driver will wait between sending two emergency start requests.
  • «common configuration options»

Gira/Insta DALI Gateway Plus REG 218000, Hager Dali gateway KNX TYA670D, Jung KNX DALI-Gateway Plus 2098/2099 REGHE, Eelectron KNX/DALI Gateway (Tunable White)

For each gateway the following configuration options are available:

  • «common configuration options»
  • Fault General (ItemId, KNX Object #1524, polled, mandatory): this communication object is true if there is an error for at least 1 DALI device.
  • Fault Short Circuit (ItemId, KNX Object #1527, optional): true if there is a general short cut on the DALI bus
  • Fault Power Failure (ItemId, KNX Object #1525, optional): true if there is a power failure on the DALI bus
  • Emergency Mode Active (ItemId, KNX Object #1541, optional): true if DALI devices are in emergency mode.
  • Emergency Lighting Failure (ItemId, KNX Object #1542, polled, optional): true if there is an error for at least 1 emergency DALI device. This config element is optional. If it is not used, emergency lighting test features are not available.
  • Error per DALI Device (ItemId, KNX Object #1544, mandatory): KNX feedback object for DALI device errors
  • EmergencyTestTimeout (int, default 10s): specifies how long the driver will wait between sending two emergency start requests.
  • «common configuration options»

The objects Fault General (#1524) and Emergency Lighting Failure (#1542) can be configure as passive or active feedback objects. If at least one of them is set as passive, "Poll Device" should be set to true.

The objects Fault General (#1524) and Error per DALI Device (#1544) needs to be linked to a group address. Otherwise the dali gateway will be seen as "not used" and therefore be ignored for the export.

Since these gateways do not have a global KNX communication object for starting an emergency test and for getting the result (they have a separate object for each device), the ItemIDs has to be configured for each emergency lighting separately. This is done in the Emergency Test Mapping.

Ipas DaliControl e64, MDT DaliControl IP Gateway SCN-DALI64.02, Merten KNX DALI-Gateway REG-K/1/16(64)/64/IP1 (MEG6725-0001), Schneider KNX DALI-Gateway MTN6725-0001, B.E.G. DALI/KNX-Gateway

For each gateway the following configuration options are available:

  • «common configuration options»
  • Fault General (ItemId, KNX Object #8, polled, mandatory): this communication object is true if there is an error for at least 1 DALI device.
  • Fault DALI (ItemId, KNX Object #9, optional): true if there is a general short cut on the DALI bus
  • Fault Lamps (ItemId, KNX Object #12, optional): true if the amount of faulty devices with a lamps fault exceeds the configured threshold.
  • Fault Ballast (ItemId, KNX Object #14, optional): true if the amount of faulty devices with a ballast fault exceeds the configured threshold.
  • Fault Converter (ItemId, KNX Object #16, optional): true if the amount of faulty emergency lights with a converter fault exceeds the configured threshold.
  • Error Status Lamp/Ballast (ItemId, KNX Object #20, mandatory)
  • EmergencyTestTimeout (int, default 10s): specifies how long the driver will wait between sending two emergency start requests.
  • «common configuration options»


 Since the communication objects #12, #14 and #16 are only getting true when a configured threshold is exceeded, it is of utmost importance to configure them correctly. In general, it is recommended to use a threshold of 1 in order to see all lamp faults.


Since these gateways do not have a global KNX communication object for starting an emergency test and for getting the result (they have a separate object for each device), the ItemIDs has to be configured for each emergency lighting separately. This is done in the Emergency Test Mapping.

Siemens KNX/DALI Gateway N 141/03, N 141/21, N 141/31

For each gateway the following configuration options are available:

  • «common configuration options»
  • Fault Power Failure (ItemId, KNX Object #34, optional)
  • Fault Devices (ItemId, KNX Object #30 or #32, polled, mandatory)
  • Fault Short Circuit (ItemId, KNX Object #31 or #33, optional)
  • Error Status (ItemId, KNX Object #37 or #736, mandatory)
  • EmergencyTestTimeout (int, default 10s): specifies how long the driver will wait between sending two emergency start requests.
  • «common configuration options»

Since these gateways do not have a global KNX communication object for starting an emergency test and for getting the result (they have a separate object for each device), the ItemIDs has to be configured for each emergency lighting separately. This is done in the Emergency Test Mapping.

Siemens KNX/DALI Gateway N 141/02

For each gateway the following configuration options are available:

  • «common configuration options»
  • Fault Power Failure (ItemId, KNX Object #6, optional)
  • Fault Devices (ItemId, KNX Object #5, polled, mandatory)
  • Fault Short Circuit (ItemId, KNX Object #7, optional)
  • Error Status (ItemId, KNX Object #11, mandatory)
  • EmergencyTestTimeout (int, default 10s): specifies how long the driver will wait between sending two emergency start requests.
  • «common configuration options»

Since these gateways do not have a global KNX communication object for starting an emergency test and for getting the result (they have a separate object for each device), the ItemIDs has to be configured for each emergency lighting separately. This is done in the Emergency Test Mapping.

Zennio DALIBOX Interface 64-32

For each gateway the following configuration options are available:

  • «common configuration options»
  • Fault Power Failure (ItemId, KNX Object #8, optional): this communication object is true if there is a power failure at the DALI gateway.
  • Fault Short Circuit (ItemId, KNX Object #9, optional): this communication object is true if there is a short circuit at the DALI bus.
  • Fault Presence (ItemId, KNX Object #10, optional): this communication object is true if at least one DALI device is missing.
  • Error Status (ItemId, KNX Object #11, mandatory): this communication object is used to request and retrieve the error status of a DALI device.
  • «common configuration options»

Emergency Test Mapping definitions

Some gateways do not have a global KNX communication object for starting an emergency test and for getting the result – they have a separate object for each device. Therefore, the ItemIDs has to be configured for each emergency lighting separately. This is done in the Emergency Test Mapping Defintions Table:

  • Name (string, mandatory): name of the Dali gateway that is used within the gateway definition.
  • Path (string, optional, default: not used): path of the Dali gateway that is used within the gateway definition.
  • DeviceId (number, mandatory): The DALI number of the device (starting with 1)
  • Start Test (ItemId, mandatory): Item that is used to start an emergency test.
    • Gira/Insta DALI Gateway Plus REG 218000, Hager Dali gateway KNX TYA670D, Jung KNX DALI-Gateway Plus 2098 REGHE: KNX Object #433 + (device ID -1) * 17 (i.e. #433, #450, #467, ...)
    • Ipas DaliControl e64, MDT DaliControl IP Gateway SCN-DALI64.02, Merten KNX DALI-Gateway REG-K/1/16(64)/64/IP1 (MEG6725-0001), Schneider KNX DALI-Gateway MTN6725-0001: KNX Object #176 + (device ID -1) * 11 (i.e. #176, #187, ...)

    • Siemens KNX/DALI Gateway N 141/03, N 141/21, N 141/31: 
      • Channel A: KNX Object #607 + (device ID -1) * 2 (i.e. #607, #609, ...)
      • Channel B: KNX Object #1306 + (device ID -1) * 2 (i.e. #1306, #1308, ...)
  • Test Result (ItemId, mandatory): Item which provides the test result. Dependening on the gateway type, the following KNX communication objects have to be used:
    • Gira/Insta DALI Gateway Plus REG 218000, Hager Dali gateway KNX TYA670D, Jung KNX DALI-Gateway Plus 2098 REGHE: KNX Object #432 + (device ID -1) * 17 (i.e. #432, #449, #466, ...)
    • Ipas DaliControl e64, MDT DaliControl IP Gateway SCN-DALI64.02, Merten KNX DALI-Gateway REG-K/1/16(64)/64/IP1 (MEG6725-0001), Schneider KNX DALI-Gateway MTN6725-0001: KNX Object #177 + (device ID -1) * 11 (i.e. #177, #188, ...)
    • Siemens KNX/DALI Gateway N 141/03, N 141/21, N 141/31: 
      • Channel A: KNX Object #608 + (device ID -1) * 2 (i.e. #608, #610, ...)
      • Channel B: KNX Object #1307+ (device ID -1) * 2 (i.e. #1307, #1309, ...)

Device Name Mapping definitions

Each DALI device behind a DALI gateway has a Server Item "Name" which shows the human-readable name of the DALI device. As default, this name has the form "Device<number>" i.e. Device1, Device2, ... This name is also used within the reports. The default name can be changed within the Device Name Mapping Defintions Table:

  • Name (string, mandatory): name of the Dali gateway that is used within the gateway definition.
  • Path (string, optional, default: not used): path of the Dali gateway that is used within the gateway definition.
  • DeviceId (number, mandatory): The DALI number of the device (starting with 1)
  • MappedName (string, mandatory): name that shall be used instead of the default name. 

Functional description

ABB DG/S 1.1

The ABB DG/S 1.1 support two DALI channels and does not support emergency lighting. However, it provides the possibility to monitor lamp and device fault of all connected DALI devices. 

Fault information is provided by three Server Items which are located directly under the gateway branch within the Server Item Tree:

  • KNX IP Connection: this Item reflects the KNXnet/IP tunneling connection to KNXnet/IP router or interface which is used to communicate with the KNX/DALI gateway.
  • Fault: true if there is either a Dali, Ballast or Lamp fault
  • Fault Dali: if true, there is a fault of the DALI communication of the channel
  • Fault Device: this communication object is true if there is a lamp or ballast failure for at least 1 DALI device.
  • Fault Ballast: if true, there is a ballast fault of one or more DALI devices on the channel. In case of a fault, LaMPS is starting to test all configured devices in order to see which device(s) have a fault. 
  • Fault Lamp:  if true, there is a lamp fault of one or more DALI devices on the channel. In case of a fault, LaMPS is starting to test all configured devices in order to see which device(s) have a fault. 

 For DALI testing, the following Server Items are available:

  • Trigger Test: this write-only Server Item is used to trigger a normal DALI test for all devices.
  • Test Running: this read-only Server Item is true when a normal DALI test is currently running.

Testing is done by used the KNX communication selected device. First, LaMPS is setting the DALI number of the device under test to the communication "Select Device" and then the KNX communication objects "Selected Device Lamp Failure" and "Selected Device Device Failure" are evaluated. If the DALI gateway sends the fault information automatically ("Change of device sends faults" is configured to "F"), LaMPS waits for the KNX telegram. If it is not pushing the information, LaMPS sends a read request.

For each configured DALI device, a sub tree with the name "Device<number>" is shown within the Server Item Tree. Each device has the following Server Items:

  • Name: human-readable name of the DALI device. The default name is "Device<number>". This name can be changed within the Device Name Mapping Definitions. 
  • Fault: if true, either a lamp or a device fault occurred.
  • Fault Lamp: true for lamp fault.
  • Fault Device: true for device fault.
  • OnOff: this item provides the current OnOff status and can be used to control the DALI device. LaMPS is using the KNX communication objects "Select Device" and "Selected Device OnOff" to provide this functionality.

ABB DG/S x.64.1.1

These KNX/DALI gateway types provide 1 or 2 DALI channels with up to 64 DALI devices. In addition to normal DALI testing, they support emergency lighting and extended tests for emergency lighting too.

For all these gateway types, the following Server Items are available:

  • KNX IP Connection: this Item reflects the KNXnet/IP tunneling connection to KNXnet/IP router or interface which is used to communicate with the KNX/DALI gateway.
  • Fault: true if there is either a Power Failure, Short Circuit, Lamp, Ballast or Converter fault
  • Fault DALI: true if there is a common DALI failure
  • Fault Device: this communication object is true if there is a lamp, ballast or converter failure for at least 1 DALI device.
  • Fault Lamps: if true, there is a lamp fault of one or more DALI devices.
  • Fault Ballast:  if true, there is a ballast fault of one or more DALI devices.  

Since these gateways also support emergency lighting, it has to be distinguished between a normal DALI test and an emergency DALI test. For normal DALI testing, the following Server Items are available:

  • Trigger Test: this write-only Server Item is used to trigger a normal DALI test for all devices.
  • Test Running: this read-only Server Item is true when a normal DALI test is currently running.

For emergency DALI testing, the following Server Items are available under the sub tree "Emergency":

  • Start Function Test: this write-only Server Item is used to trigger a function test for all emergency DALI lights.
  • Start Duration Test: this write-only Server Item is used to trigger a duration test for all emergency DALI lights.
  • Start Partial Duration Test: this write-only Server Item is used to trigger a partial duration test for all emergency DALI lights.
  • Start Battery Test: this write-only Server Item is used to trigger a battery test for all emergency DALI lights.
  • Emergency Light Test Running: this read-only Server Item is true when an emergency DALI test is currently running.

Please keep in mind that these items will only appear when emergency testing is available for the gateway. For these KNX/DALI gateways the "Emergency Test Start (#32, #40 or #1154)" and "Emergency Test Result (#33, #42 or #1156)" objects must be available and configured in order to support emergency testing. Note that emergency testing is only available for self contained battery lamps.


For each configured DALI device, a sub tree with the name "Device<number>" is shown within the Server Item Tree. Each device has at least the following Server Items:

  • Name: human-readable name of the DALI device. The default name is "Device<number>". This name can be changed within the Device Name Mapping Definitions. 
  • Fault: if true, either a lamp or a device fault occurred.
  • Fault Lamp: true for lamp fault.
  • Fault Ballast: true for ballast fault.
  • Test Supported: true if a response is received during the test

If emergency functions are available, the following items are available in the sub tree "Emergency":

  • Test Running:  this read-only Server Item is true when an emergency DALI test is currently running.
  • Start Function Test: this write-only Server Item is used to trigger a function test for this device.
  • Start Duration Test: this write-only Server Item is used to trigger a duration test for this device.
  • Start Partial Duration Test: this write-only Server Item is used to trigger a partial duration test for this device.
  • Start Battery Test: this write-only Server Item is used to trigger a battery test for this device.
  • Last test was: shows the test type of the last test result. 0 for "No Test", 1 for "Function Test", 2 for "Partial duration test", 3 for "Duration test", 4 for "Battery test" and 255 for "Test not supported".
  • Last test faulted: true if there was no test result response. This may be the case when the DALI does not support emergency tests.
  • Circuit defect: true if the circuit is defect

  • Fault battery: true if there is a battery fault

  • Battery defect: true if the battery is defect

  • Fault emergency light: true if there is an emergency light failure

  • Function test triggered but not executed: true if a function test was triggered but not finished

  • Duration test triggered but not executed: true if a Duration test was triggered but not finished

  • Function test failed: true if the function test failed

  • Duration test failed: true if the duration test failed

  • TestResult: test result

ABB DGN/S 1.16.1

These KNX/DALI gateway types provide 1 with up to 64 DALI devices. In addition to normal DALI testing, they support emergency lighting and extended tests for emergency lighting too.

For all these gateway types, the following Server Items are available:

  • KNX IP Connection: this Item reflects the KNXnet/IP tunneling connection to KNXnet/IP router or interface which is used to communicate with the KNX/DALI gateway.
  • Fault: true if there is either a power failure, short circuit, lamp, ballast or converter fault
  • Fault DALI: true if there is a common DALI failure
  • Fault Device: this communication object is true if there is a lamp, ballast or converter failure for at least 1 DALI device.
  • Fault Lamps: if true, there is a lamp fault of one or more DALI devices.
  • Fault Ballast:  if true, there is a ballast fault of one or more DALI devices.  

Since these gateways also support emergency lighting, it has to be distinguished between a normal DALI test and an emergency DALI test. For normal DALI testing, the following Server Items are available:

  • Trigger Test: this write-only Server Item is used to trigger a normal DALI test for all devices.
  • Test Running: this read-only Server Item is true when a normal DALI test is currently running.

For emergency DALI testing, the following Server Items are available under the sub tree "Emergency":

  • Start Function Test: this write-only Server Item is used to trigger a function test for all emergency DALI lights.
  • Start Duration Test: this write-only Server Item is used to trigger a duration test for all emergency DALI lights.
  • Start Partial Duration Test: this write-only Server Item is used to trigger a partial duration test for all emergency DALI lights.
  • Start Battery Test: this write-only Server Item is used to trigger a battery test for all emergency DALI lights.
  • Emergency Light Test Running: this read-only Server Item is true when an emergency DALI test is currently running.

Please keep in mind that these items will only appear when emergency testing is available for the gateway. For these KNX/DALI gateways the "Emergency Test Start (#32, #40 or #1154)" and "Emergency Test Result (#33, #42 or #1156)" objects must be available and configured in order to support emergency testing. Note that emergency testing is only available for self contained battery lamps.

For each configured DALI device, a sub tree with the name "Device<number>" is shown within the Server Item Tree. Each device has at least the following Server Items:

  • Name: human-readable name of the DALI device. The default name is "Device<number>". This name can be changed within the Device Name Mapping Definitions. 
  • Fault: if true, either a lamp or a device fault occurred.
  • Fault Lamp: true for lamp fault.
  • Fault Ballast: true for ballast fault.
  • Test Supported: true if a response is received during the test

If emergency functions are available, the following items are available in the sub tree "Emergency":

  • Test Running:  this read-only Server Item is true when an emergency DALI test is currently running.
  • Start Function Test: this write-only Server Item is used to trigger a function test for this device.
  • Start Duration Test: this write-only Server Item is used to trigger a duration test for this device.
  • Start Partial Duration Test: this write-only Server Item is used to trigger a partial duration test for this device.
  • Start Battery Test: this write-only Server Item is used to trigger a battery test for this device.
  • Last test was: shows the test type of the last test result. 0 for "No Test", 1 for "Function Test", 2 for "Partial duration test", 3 for "Duration test", 4 for "Battery test" and 255 for "Test not supported".
  • Last test faulted: true if there was no test result response. This may be the case when the DALI does not support emergency tests.
  • Circuit defect: true if the circuit is defect

  • Fault battery: true if there is a battery fault

  • Battery defect: true if the battery is defect

  • Fault emergency light: true if there is an emergency light failure

  • Function test triggered but not executed: true if a function test was triggered but not finished

  • Duration test triggered but not executed: true if a Duration test was triggered but not finished

  • Function test failed: true if the function test failed

  • Duration test failed: true if the duration test failed

  • TestResult: test result

EAE DA 100/110

These KNX/DALI gateway types provide 1 with up to 64 DALI devices. In addition to normal DALI testing, they support emergency lighting and extended tests for emergency lighting too.

For all these gateway types, the following Server Items are available:

  • KNX IP Connection: this Item reflects the KNXnet/IP tunneling connection to KNXnet/IP router or interface which is used to communicate with the KNX/DALI gateway.
  • Fault: true if there is either a power failure, short circuit, lamp, ballast or converter fault
  • Fault Gateway Supply: true if there is a gateway supply error within the DALI gateway
  • Fault Mains Supply: true if there is a main supply error within the DALI gateway
  • Fault Device: this communication object is true if there is a lamp, ballast or converter failure for at least 1 DALI device.
  • Fault Lamps: if true, there is a lamp fault of one or more DALI devices.
  • Fault Ballast:  if true, there is a ballast fault of one or more DALI devices.  
  • Fault Converter: this item is only available for at least one DALI device that supports emergency lighting. If true, there is a converter fault of one or more DALI devices.

Since these gateways also support emergency lighting, it has to be distinguished between a normal DALI test and an emergency DALI test. For normal DALI testing, the following Server Items are available:

  • Trigger Test: this write-only Server Item is used to trigger a normal DALI test for all devices.
  • Test Running: this read-only Server Item is true when a normal DALI test is currently running.

For emergency DALI testing, the following Server Items are available under the sub tree "Emergency":

  • Start Function Test: this write-only Server Item is used to trigger a function test for all emergency DALI lights.
  • Start Duration Test: this write-only Server Item is used to trigger a duration test for all emergency DALI lights.
  • Emergency Light Test Running: this read-only Server Item is true when an emergency DALI test is currently running.

Please keep in mind that these items will only appear when emergency testing is available for the gateway. For these KNX/DALI gateways the "Fault converter (#14 or #16)" object must be available and configured in order to support emergency testing. Note that emergency testing is only available for self contained battery lamps.

For each configured DALI device, a sub tree with the name "Device<number>" is shown within the Server Item Tree. Each device has at least the following Server Items:

  • Name: human-readable name of the DALI device. The default name is "Device<number>". This name can be changed within the Device Name Mapping Definitions. 
  • Fault: if true, either a lamp or a device fault occurred.
  • Fault Lamp: true for lamp fault.
  • Fault Ballast: true for ballast fault.
  • Fault Convert: true for converter fault. Only available for emergency lights
  • Test Supported: true if a response is received during the test

If emergency functions are available, the following items are available in the sub tree "Emergency":

  • Test Running:  this read-only Server Item is true when an emergency DALI test is currently running.
  • Start Function Test: this write-only Server Item is used to trigger a function test for this device.
  • Start Duration Test: this write-only Server Item is used to trigger a duration test for this device.
  • Last test faulted: true if there was no test result response. This may be the case when the DALI does not support emergency tests.
  • Battery defect: true if the battery is defect

  • Fault emergency light: true if there is an emergency light failure

  • Function test failed: true if the function test failed

  • Duration test failed: true if the duration test failed

Gira/Insta DALI Gateway Plus REG 218000, Hager Dali gateway KNX TYA670D, Jung KNX DALI-Gateway Plus 2098/2099 REGHE, Eelectron KNX/DALI Gateway (Tunable White)

These KNX/DALI gateway types provide 1 DALI channel with up to 64 DALI devices. In addition to normal DALI testing, they support emergency lighting and extended tests for emergency lighting too.

For all these gateway types, the following Server Items are available:

  • KNX IP Connection: this Item reflects the KNXnet/IP tunneling connection to KNXnet/IP router or interface which is used to communicate with the KNX/DALI gateway.
  • Fault: true if there is either a Power Failure, Short Circuit, Lamp, Ballast or Converter fault
  • Fault Short Circuit: true if there is a general short cut on the DALI bus
  • Fault Power Failure: true if there is a power failure on the DALI bus
  • Fault Device: this communication object is true if there is a lamp, ballast or converter failure for at least 1 DALI device.If configured, LaMPS is starting to test all configured devices in order to see which device(s) have a fault.
  • Fault Lamps: if true, there is a lamp fault of one or more DALI devices.  
  • Fault Ballast:  if true, there is a ballast fault of one or more DALI devices.  
  • Fault Converter: this item is only available for at least one DALI device that supports emergency lighting. If true, there is a converter fault of one or more DALI devices.

Since these gateways also support emergency lighting, it has to be distinguished between a normal DALI test and an emergency DALI test. For normal DALI testing, the following Server Items are available:

  • Trigger Test: this write-only Server Item is used to trigger a normal DALI test for all devices.
  • Test Running: this read-only Server Item is true when a normal DALI test is currently running.

For emergency DALI testing, the following Server Items are available under the sub tree "Emergency":

  • Emergency Mode Active: true if the gateway is in emergency mode
  • Emergency Lighting Failure: true there is an emergency failure of at least one emergency DALI light
  • Start Function Test: this write-only Server Item is used to trigger a function test for all emergency DALI lights.
  • Start Duration Test: this write-only Server Item is used to trigger a duration test for all emergency DALI lights.
  • Start Partial Duration Test: this write-only Server Item is used to trigger a partial duration test for all emergency DALI lights.
  • Start Battery Test: this write-only Server Item is used to trigger a battery test for all emergency DALI lights.
  • Stop Test: this write-only Server Item is used to stop a running test.
  • Emergency Light Test Running: this read-only Server Item is true when an emergency DALI test is currently running.

Please keep in mind that these items will only appear when emergency testing is available for the gateway. For these KNX/DALI gateways at least one DALI device must support emergency lighting tests. This means that there must be a "Emergency Mapping Definition" for at least one DALI device. Note that emergency testing is only available for self contained battery lamps.

For each configured DALI device, a sub tree with the name "Device<number>" is shown within the Server Item Tree. Each device has at least the following Server Items:

  • Name: human-readable name of the DALI device. The default name is "Device<number>". This name can be changed within the Device Name Mapping Definitions. 
  • Fault: if true, either a lamp or a device fault occurred.
  • Fault Lamp: true for lamp fault.
  • Fault Ballast: true for ballast fault.
  • Fault Converter: this item is only available if emergency lighting is supported. If true, there is a converter fault.
  • Test Supported: true if a response is received during the test

If a device is also an emergency light (i.e. it has a valid emergency mapping definition), the following items are available in the sub tree "Emergency":

  • Test Running:  this read-only Server Item is true when an emergency DALI test is currently running.
  • Start Function Test: this write-only Server Item is used to trigger a function test for this device.
  • Start Duration Test: this write-only Server Item is used to trigger a duration test for this device.
  • Start Partial Duration Test: this write-only Server Item is used to trigger a partial duration test for this device.
  • Start Battery Test: this write-only Server Item is used to trigger a battery test for this device.
  • Last test was: shows the test type of the last test result. 0 for "No Test", 1 for "Function Test", 2 for "Partial duration test", 3 for "Duration test", 4 for "Battery test" and 255 for "Test not supported".
  • Last test faulted: true if there was no test result response. This may be the case when the DALI does not support emergency tests.
  • Circuit defect: true if the circuit is defect

  • Fault battery: true if there is a battery fault

  • Battery defect: true if the battery is defect

  • Fault emergency light: true if there is an emergency light failure

  • Max time function test exceeded: true if the maximum time for the function test exceeded

  • Max time duration test exceeded: true if the maximum time for the duration exceeded

  • Function test failed: true if the function test failed

  • Duration test failed: true if the duration test failed

  • TestResult: test result

Ipas DaliControl e64, MDT DaliControl IP Gateway SCN-DALI64.02, Merten KNX DALI-Gateway REG-K/1/16(64)/64/IP1 (MEG6725-0001), Schneider KNX DALI-Gateway MTN6725-0001, B.E.G. DALI/KNX-Gateway

These KNX/DALI gateway types provide 1 DALI channel with up to 64 DALI devices. In addition to normal DALI testing, they support emergency lighting and extended tests for emergency lighting too.

For all these gateway types, the following Server Items are available:

  • KNX IP Connection: this Item reflects the KNXnet/IP tunneling connection to KNXnet/IP router or interface which is used to communicate with the KNX/DALI gateway.
  • Fault: true if there is either a DALI, lamp, or ballast fault
  • Fault DALI: true if there is a general short cut on the DALI bus
  • Fault Device: this communication object is true if there is a lamp or ballast fault for at least 1 DALI device.
  • Fault Lamps: if true, the amount of lamp faults exceeds the configured threshold. If exceeded, LaMPS is starting to test all configured devices in order to see which device(s) have a fault. 
  • Fault Ballast:  if true, the amount of ballast faults exceeds the configured threshold. If exceeded, LaMPS is starting to test all configured devices in order to see which device(s) have a fault. 

Since these gateways also support emergency lighting, it has to be distinguished between a normal DALI test and an emergency DALI test. For normal DALI testing, the following Server Items are available:

  • Trigger Test: this write-only Server Item is used to trigger a normal DALI test for all devices.
  • Test Running: this read-only Server Item is true when a normal DALI test is currently running.

For emergency DALI testing, the following Server Items are available under the sub tree "Emergency":

  • Fault Converter: true there is the amount emergency failures exceeds the configured threshold.
  • Start Function Test: this write-only Server Item is used to trigger a function test for all emergency DALI lights.
  • Start Duration Test: this write-only Server Item is used to trigger a duration test for all emergency DALI lights.
  • Start Partial Duration Test: this write-only Server Item is used to trigger a partial duration test for all emergency DALI lights.
  • Start Battery Test: this write-only Server Item is used to trigger a battery test for all emergency DALI lights.
  • Stop Test: this write-only Server Item is used to stop a running test.
  • Emergency Light Test Running: this read-only Server Item is true when an emergency DALI test is currently running.

Please keep in mind that these items will only appear when emergency testing is available for the gateway. For these KNX/DALI gateways at least one DALI device must support emergency lighting tests. This means that there must be a "Emergency Mapping Definition" for at least one DALI device. Note that emergency testing is only available for self contained battery lamps.

For each configured DALI device, a sub tree with the name "Device<number>" is shown within the Server Item Tree. Each device has at least the following Server Items:

  • Name: human-readable name of the DALI device. The default name is "Device<number>". This name can be changed within the Device Name Mapping Definitions. 
  • Fault: if true, either a lamp or a device fault occurred.
  • Fault Lamp: true for lamp fault.
  • Fault Ballast: true for device fault.
  • Test Supported: true if a response is received during the test

If a device is also an emergency light (i.e. it has a valid emergency mapping definition), the following items are available in the sub tree "Emergency":

  • Test Running:  this read-only Server Item is true when an emergency DALI test is currently running.
  • Start Function Test: this write-only Server Item is used to trigger a function test for this device.
  • Start Duration Test: this write-only Server Item is used to trigger a duration test for this device.
  • Start Partial Duration Test: this write-only Server Item is used to trigger a partial duration test for this device.
  • Start Battery Test: this write-only Server Item is used to trigger a battery test for this device.

Siemens KNX/DALI Gateway N 141/03, N 141/21, N 141/31, N 141/02

These KNX/DALI gateway types provide 1 or 2 DALI channels with up to 64 DALI devices. In addition to normal DALI testing, they support emergency lighting and extended tests for emergency lighting too.

For all these gateway types, the following Server Items are available:

  • KNX IP Connection: this Item reflects the KNXnet/IP tunneling connection to KNXnet/IP router or interface which is used to communicate with the KNX/DALI gateway.
  • Fault: true if there is either a power failure, short circuit, lamp, ballast or converter fault.
  • Fault Power Failure: true if there is a power failure within the DALI gateway.
  • Fault Short Circuit: true if there is a general short cut on the DALI channel.
  • Fault Device: this communication object is true if there is a lamp, ballast or converter failure for at least 1 DALI device.
  • Fault Lamps: if true, there is a lamp fault of one or more DALI devices.
  • Fault Ballast:  if true, there is a ballast fault of one or more DALI devices.  
  • Fault Converter: this item is only available for at least one DALI device that supports emergency lighting. If true, there is a converter fault of one or more DALI devices.

Since these gateways also support emergency lighting, it has to be distinguished between a normal DALI test and an emergency DALI test. For normal DALI testing, the following Server Items are available:

  • Trigger Test: this write-only Server Item is used to trigger a normal DALI test for all devices.
  • Test Running: this read-only Server Item is true when a normal DALI test is currently running.

For emergency DALI testing, the following Server Items are available under the sub tree "Emergency":

  • Start Function Test: this write-only Server Item is used to trigger a function test for all emergency DALI lights.
  • Start Duration Test: this write-only Server Item is used to trigger a duration test for all emergency DALI lights.
  • Start Partial Duration Test: this write-only Server Item is used to trigger a partial duration test for all emergency DALI lights.
  • Start Battery Test: this write-only Server Item is used to trigger a battery test for all emergency DALI lights.
  • Emergency Light Test Running: this read-only Server Item is true when an emergency DALI test is currently running.

Please keep in mind that these items will only appear when emergency testing is available for the gateway. For these KNX/DALI gateways at least one DALI device must support emergency lighting tests. This means that there must be a "Emergency Mapping Definition" for at least one DALI device. Note that emergency testing is only available for self contained battery lamps.

For each configured DALI device, a sub tree with the name "Device<number>" is shown within the Server Item Tree. Each device has at least the following Server Items:

  • Name: human-readable name of the DALI device. The default name is "Device<number>". This name can be changed within the Device Name Mapping Definitions. 
  • Fault: if true, either a lamp or a device fault occurred.
  • Fault Lamp: true for lamp fault.
  • Fault Ballast: true for ballast fault.
  • Fault Converter: this item is only available if emergency lighting is supported. If true, there is a converter fault.
  • Test Supported: true if a response is received during the test

If a device is also an emergency light (i.e. it has a valid emergency mapping definition), the following items are available in the sub tree "Emergency":

  • Test Running:  this read-only Server Item is true when an emergency DALI test is currently running.
  • Start Function Test: this write-only Server Item is used to trigger a function test for this device.
  • Start Duration Test: this write-only Server Item is used to trigger a duration test for this device.
  • Start Partial Duration Test: this write-only Server Item is used to trigger a partial duration test for this device.
  • Start Battery Test: this write-only Server Item is used to trigger a battery test for this device.
  • Last test was: shows the test type of the last test result. 0 for "No Test", 1 for "Function Test", 2 for "Partial duration test", 3 for "Duration test", 4 for "Battery test" and 255 for "Test not supported".
  • Last test faulted: true if there was no test result response. This may be the case when the DALI does not support emergency tests.
  • Circuit defect: true if the circuit is defect

  • Fault battery: true if there is a battery fault

  • Battery defect: true if the battery is defect

  • Fault emergency light: true if there is an emergency light failure

  • Max time function test exceeded: true if the maximum time for the function test exceeded

  • Max time duration test exceeded: true if the maximum time for the duration exceeded

  • Function test failed: true if the function test failed

  • Duration test failed: true if the duration test failed

  • TestResult: test result

Zennio DALIBOX Interface 64-32

The Zennio DALIBOX Interface 64-32 supports one DALI channel with up to 64 DALI devices.

Fault information is provided by the following Server Items which are located directly under the gateway branch within the Server Item Tree:

  • KNX IP Connection: this Item reflects the KNXnet/IP tunneling connection to KNXnet/IP router or interface which is used to communicate with the KNX/DALI gateway.
  • Fault: true if there is either a power failure, short circuit, presence, ballast or lamp fault.
  • Fault Power Failure: true if there is a power failure within the DALI gateway.
  • Fault Short Circuit: true if there is a general short circuit on the DALI channel.
  • Fault Presence: true if at least one DALI device is missing on the channel.
  • Fault Device: this communication object is true if there is a lamp or ballast failure for at least 1 DALI device.
  • Fault Ballast: if true, there is a ballast fault of one or more DALI devices on the channel. 
  • Fault Lamp:  if true, there is a lamp fault of one or more DALI devices on the channel. 

 For DALI testing, the following Server Items are available:

  • Trigger Test: this write-only Server Item is used to trigger a normal DALI test for all devices.
  • Test Running: this read-only Server Item is true when a normal DALI test is currently running.

For each configured DALI device, a sub tree with the name "Device<number>" is shown within the Server Item Tree. Each device has the following Server Items:

  • Name: human-readable name of the DALI device. The default name is "Device<number>". This name can be changed within the Device Name Mapping Definitions. 
  • Fault: if true, either a lamp or a ballast fault occurred.
  • Fault Lamp: true for lamp fault.
  • Fault Ballast: true for ballast fault.
  • Test Supported: true if a response is received during the test