Siemens KNX/DALI Gateway N 141/02
Configuration
In addition to the common configuration options the following configuration options are available for each channel:
parameter | type | optional/mandatory | communication object | description | default |
---|---|---|---|---|---|
Fault Power Failure | ItemId | O | KNX Object #6 | True, if there is a power failure on the DALI bus. | |
Fault Devices | ItemId | M | KNX Object #5, polled | True, if there is a lamp or ballast failure for at least 1 DALI device. | |
Fault Short Circuit | ItemId | O | KNX Object #7 | True, if there is a general short cut on the DALI bus. | |
Error Status | ItemId | M | KNX Object #11 | ||
Emergency Test Interval | int | O | Specifies how long the driver will wait between sending two emergency start requests. | 10 s |
Since these gateways do not have a global KNX communication object for starting an emergency test and for getting the result (they have a separate object for each device), the ItemIDs has to be configured for each emergency lighting separately. This is done in the Emergency Test Mapping.
Functional description
refer to Siemens KNX/DALI Gateway N 141/03, N 141/21, N 141/31