OPC UA Datapoint Definitions

The Core Server polls the information of the OPC UA Server. The received data is finally represented as server items.

File Location

<WorkspaceDirectory>\DataFiles\xio.OpcUa.DatapointDefinitions.dat

Col#

Parameter 

Description

Scope

Unit

Mandatory / default value

Col#

Parameter 

Description

Scope

Unit

Mandatory / default value

1

Server Name

The full name of the remote OPC UA server. This must match the combination name and path from the server definitions.

string

none

mandatory

2

Name

The name of the data point. The combination of name and path must be unique within this definition file.

string

none

mandatory

3

Path

The generated path in Item Tree. The combination of name and path must be unique within this definition file.

string

none

empty

4

Namespace Index

The index of the namespace URI in the namespace array.

string

none

empty

5

Nodeld type

The type of the Node ID (by default String). 

uint, guid, string

none

String

6

Nodeld Value

The node ID of the data point. 

string

none

empty

7

Data Type

The data type of the data point.

BOOL, STR, BYTE, CHAR, INT8, UINT8, INT16, UINT16, INT32, UINT32, INT64, UINT64, FLOAT, DOUBLE, DATE, TIME

none

String

8

Access Mode

This parameters specifies the access mode of the data point on the server. 

ReadOnly, WriteOnly, ReadWrite

none

ReadOnly

9

Persistent

This parameter specifies whether the value of the data point is persistent (restored from the database after server start up) or not.

true/false

none

false

10

Synchronize

If set to True (T), the value is synchronized between the main and backup server (if present).

true/false

none

true

 