OPC UA Server Definitions

To communicate with an OPC UA server, this information has to be defined. The server definition specifies the appropriate information to connect with an OPC UA server.

File location

<WorkspaceDirectory>\DataFiles\xio.OpcUa.ServerDefinitions.dat

Col#

Parameter 

Description

Scope

Unit

Mandatory / default value

Col#

Parameter 

Description

Scope

Unit

Mandatory / default value

1

Name

The given name of the OPC UA server in the NETx Server. The combination of name and path must be unique within this definition file.

string

none

mandatory

2

Path

The generated path in the Item Tree. The combination of name and path must be unique within this definition file. 

string

none

empty

3

URL

The URL of the OPC UA Server.

string

none

empty

4

User Security

If set to true, a secure connection will be used to connect to the OPC UA server.

true/false

none

false

5

Add Unknown Certificates

If enabled, unknown certificates are accepted by the OPC UA client implementation. If disabled, the certificate must be trusted by this computer. A trusted certificate must be either an official certificate or the CA certificate must be located in the certificate store of the local computer (path  "Local Computer\NETx BMS Platform").

true/false

none

True

6

Username

If the OPC UA Server requires authentication, the username must be specified here.

string

none

String

7

Password

If the OPC UA Server requires authentication, the password must be specified here.

string

none

String

8

Write Timestamps

Choose which timestamps shall be used for writing to OPC UA data points.

Neither, Source, Server, Both

none

Neither

9

Subscription Delay

Delay between the successful connect to the OPC UA service and the subscription request. This option is useful when the OPC UA nodes are not immediately available after starting an OPC UA server.

0 – 600

seconds

0

 