Helvar sub device definitions

Within this definition file, the Helvar sub devices can be configured.

File location

<WorkspaceDirectory>\DataFiles\xio.HelvarNet.SubDevices.dat

Each sub device has its own row with the parameters separated by a semicolon. (CSV-format)

The interface configuration can be edited in the NETx Core Server Studio at HelvarNet > Sub Device Definitions

Col#

Parameter

Description

Scope

Unit

Mandatory / default value

Col#

Parameter

Description

Scope

Unit

Mandatory / default value

1

Device address

Address of the device to which the sub device belongs too. Reference to Helvar device definitions

string

None

mandatory

2

Id

ID of sub device.

string

None

mandatory

3

Poll Measurement

If activated, the measurement is polled.

true/false

None

false

4

Poll Input

If activated, the input is polled.

true/false

None

false

5

Polling Interval

Interval for polling the measurement and / or input (in seconds). 0 means polling is deactivated.

seconds

0 – 65535

0