Emergency testing server items per DALI gateway
Emergency testing server items per DALI gateway
For DALI emergency testing, the following Server Items are available under the Emergency branch:
item name | access | description |
---|---|---|
Start Function Test | W | Used to trigger a function test for all emergency DALI lights. |
Start Partial Duration Test | W | Used to trigger a partial duration test for all emergency DALI lights. |
Start Duration Test | W | Used to trigger a duration test for all emergency DALI lights. |
Start Battery Test | W | Used to trigger a battery test for all emergency DALI lights. |
Test faulty devices only | RW | If set to True when a test is triggered, only DALI devices that failed the previous test will be submitted to the test. |
Test Triggered | R |
Use this data point as a callback to indicate that a test has been triggered. |
Test Running | R | True, if an emergency DALI test is currently running. |
Stop Test | W | Used to stop a running test. |
Remaining Test Runtime | R | The remaining runtime in minutes of a triggered test. |
Number Faulty Devices | R | The number of devices that failed on the latest test. |
Faulty devices | R | Comma-separated list of device numbers of devices that did not pass the latest test. |
Fault | R | True, if an emergency test of at least 1 DALI light failed. |
Last test was | R | Shows the type of the last completed test, according to LaMPS test type encoding. |
Last test faulted | R | True, if "Last test faulted" of at least 1 DALI light is currently true. |
Last test stopped | R | True, if "Last test stopped" of at least 1 DALI light is currently true. |
Converter defect | R | True, if "Converter defect" of at least 1 DALI light is currently true. |
Battery fault or defect | R | True, if "Battery fault or defect" of at least 1 DALI light is currently true. |
Fault emergency light | R | True, if "Fault emergency light" of at least 1 DALI light is currently true. |