UPS definitions
Access: Core Studio > Modules > LaMPS > DALI > UPS definitions
File location: <WorkspaceDirectory>\DataFiles\xio.LaMPS.UpsDefinitions.dat
Each row in the table specifies a UPS device.
Col# | Parameter | Description | Scope | Unit | Default value |
---|---|---|---|---|---|
1 | Name | UPS name | String | None |
|
2 | Path | Path inside NETx\Module\LaMPS\UPS | String | None | empty |
3 | Battery level | Data point that holds the charge level of the UPS battery in percent. | ItemID | None | empty |
4 | Battery level threshold | Data point that holds the battery charge threshold. Levels below the threshold lead UPS tests to be considered as failed. | ItemID | None | empty |
5 | Battery level manual override | If enabled, a manual override of the battery charge level device reading is written to the database. | Boolean | None | False |
6 | Function test duration | Duration of the UPS function test. | Numeric | min | 10 |
7 | Partial duration test duration | Duration of the UPS partail duration test. | Numeric | min | 240 |
8 | Test start delay | Interval that is awaited after a test was triggered before the test is started. | Numeric | s | 10 |